Operation
Test modes
There are 2 methods in which the "Test" mode can be cycled with the test button:
1. Step Test Mode
This method initiates the different components of the unit, one at a time, by temporarily shorting across the two test terminals for two to three seconds. For the initial start- up of the unit, this method allows the technician to cycle a component "On" and have up to 1 hour to complete the check.
2. Auto Test Mode
This method is not recommended for
For unit test steps and test modes, values to cycle the various components, refer to Table 36.
Table 36 - Service Test Guide for Component Operation on
Step | Mode | Indoor | Economizer | Compressor | Compressor | Heat 1 | Heat 2 | Outdoor 1 | Outdoor 2 |
|
| Fan |
| 1 | 2 |
|
|
|
|
1 | Fan On | On | Min | Off | Off | Off | Off | Off | Off |
|
|
|
|
|
|
|
|
|
|
2* | Econ. | On | Open | Off | Off | Off | Off | Off | Off |
|
|
|
|
|
|
|
|
|
|
3 | CooI1 | On | Min | On | Off | Off | Off | On | ** |
|
|
|
|
|
|
|
|
|
|
4 | CooI2 | On | Min | On | On | Off | Off | On | ** |
|
|
|
|
|
|
|
|
|
|
5 | Heat1 | On | Min | Off | Off | On | Off | Off | Off |
|
|
|
|
|
|
|
|
|
|
6 | Heat2 | On | Min | Off | Off | On | On | Off | Off |
*With Optional Accessory
**"Off" If temperature falls below 16° (±1°)°C, "On" if temperature rises above 18°(±1°)°C. Note: Steps for optional accessories and modes not present in unit will be skipped.
50 |