Operation

Test procedures

Operating checklist before start-up

Unit is level, with sufficient clearance all round

Duct network is correctly sized according to the unit configuration, insulated, and water-tight

Condensate drainage line is correctly sized, equipped with a trap, and sloped

Filters are in position, of correct size and quantity and clean

Wiring is correctly sized and connected in accordance with wiring diagrams

Power supply lines are protected by recommended fuses and correctly earthed

Thermostat is correctly wired and positioned

Unit is checked for refrigerant charge and leaks

Indoor and outdoor fans rotate freely and are fixed on shafts

Supply fan rotation speed is set

Access panels and doors are replaced to prevent air entering and risks of injury

Checking of the gas heating section, in accordance with above procedure

WARNING! If any operating checks must be performed with the unit operating, it is the technician's responsibility to recognize any possible hazards and proceed in a safe manner. Failure to do so could result in severe personal injury or death due to electrical shock or contact with moving parts.

Power-up initialization

CAUTION! Before proceeding with any test procedure or operation, make sure that crankcase heaters have been energized for at least 8 hours.

Units equipped with Scroll compressors do not have crankcase heaters.

Note:

Upon power initialization, the RTRM performs self-diagnostic checks to insure that all internal controls are functional. It also checks the configuration parameters against the components connected to the system. The Liteport LED located on the RTRM module is turned "On" within 1 second of power-up if internal operation is okay.

Test mode procedure at the ReliaTel™ control board

Operating the unit from the roof using the test mode at the ReliaTel™ control board.

CAUTION! Before proceeding with the following test procedures, make sure that thermostat or zone sensor is off.

CAUTION! Use one of the following "Test" procedures to bypass some time delays and to start the unit at the control panel.

Each step of unit operation can be activated individually by temporarily shorting across the "Test" terminals for two to three seconds. The Liteport LED located on the RTRM module will blink when the test mode has been initiated. The unit can be left in any "Test" step for up to one hour before it will automatically terminate, or it can be terminated by opening the main power disconnect switch. Once the test mode has been terminated, the Liteport LED will glow continuously and the unit will revert to the "System" control.

RT-SVX19A-E4

49

Page 49
Image 49
Trane RT-SVX19A-E4 manual Test procedures, Power-up initialization, Test mode procedure at the ReliaTel control board

RT-SVX19A-E4 specifications

The Trane RT-SVX19A-E4 is a groundbreaking rooftop unit designed for versatile commercial heating and cooling applications. This model stands out for its innovative technology and robust features, making it a preferred choice for many businesses seeking efficient climate control solutions.

One of the primary characteristics of the RT-SVX19A-E4 is its exceptional energy efficiency. It utilizes advanced variable-speed technology, allowing it to adjust the compressor's output based on real-time demand. This not only reduces energy consumption significantly but also provides more accurate temperature control, enhancing overall comfort within the space. The unit is designed with high-efficiency fan motors and optimized heat exchangers, which contribute to its impressive Seasonal Energy Efficiency Ratio (SEER) and Energy Efficiency Ratio (EER) ratings.

The Trane RT-SVX19A-E4 also features a robust and durable design, built to withstand a variety of weather conditions. Its all-weather cabinet protects the internal components from environmental stresses, ensuring longevity and reliable performance. The unit is equipped with corrosion-resistant materials that enhance its durability, making it suitable for both coastal and urban environments.

Another notable feature is its advanced control system. The RT-SVX19A-E4 comes with Trane's IntelliPak controls, which provide users with precise monitoring and management capabilities. This smart control system enables remote access via internet connectivity, allowing facility managers to monitor performance, adjust settings, and diagnose issues in real-time, improving operational efficiency and reducing maintenance costs.

Additionally, the RT-SVX19A-E4 offers a range of customization options. It can be tailored to meet specific operational needs, with various configurations available for air flow, heating, and cooling needs. This flexibility ensures organizations can find a solution that best fits their requirements, whether it be for an office building, retail space, or industrial facility.

In conclusion, the Trane RT-SVX19A-E4 represents a significant advancement in rooftop HVAC technology, combining energy efficiency, durability, and intelligent controls. Its ability to adapt to varying demands, coupled with customizable options, makes it an excellent investment for businesses looking to enhance their indoor climate while minimizing energy expenses.