Performance Data

Discharge Plenum and Grille Assembly Throw Distance

Table 30. Discharge Plenum and Grille Assembly Throw Distance (ft) — Air Handler

 

 

 

 

Louver Angle Deflection Position

 

Tons

Model No.

CFM

 

 

 

 

Straight

20°

40°

55°

 

 

 

 

 

 

 

 

 

1600

42

31

26

20

 

TWE060A

1800

46

37

29

22

5

TWE060B

2000

48

43

33

24

 

 

2200

51

50

36

25

 

 

2400

54

57

39

29

 

 

 

 

 

 

 

 

 

2400

52

43

35

29

 

TWE090A

2700

55

48

38

31

TWE090B

3000

58

53

42

32

 

 

3300

62

57

46

35

 

 

3600

66

60

50

37

 

 

 

 

 

 

 

 

 

3200

56

46

38

30

 

TWE120A

3600

62

51

42

33

10

TWE120B

4000

66

57

47

35

 

 

4400

71

62

52

38

 

 

4800

76

67

56

42

 

 

 

 

 

 

 

 

 

4900

47

38

32

25

 

TWE180B

5400

52

44

37

29

15

 

6000

57

49

41

32

 

 

6600

61

53

43

34

 

 

7200

65

57

46

35

 

 

 

 

 

 

 

 

 

6400

56

46

38

30

 

TWE240B/

7200

62

51

42

33

20

TWE240E

8000

66

57

47

35

 

 

8800

71

62

52

38

 

 

9600

76

67

56

42

Notes:

1.Throw distance values are based on a terminal velocity of 75 FPM.

2.Throw distance values at other terminal velocities may be established by multiplying throw distances in the table above by throw factor

Terminal

Throw

Velocity

Factor

 

 

50 FPM

x 1.50

100 FPM

x .75

150 FPM

x .50

SSP-PRC001-EN