Mechanical Specifications

Heat Pumps

General

Units shall be assembled on heavy gauge steel mounting/lifting rails and shall be weather proofed. Unit shall include a hermetic scroll or reciprocating compressor(s), plate fin condenser coil, fans and motors, controls and holding charge of nitrogen. Operating Range shall be between 115°F to 50°F in cooling as standard from factory. Units shall be UL 1995 listed and rated in accordance with ARI Standard 340/ 360.

Casing

Unit casing shall be constructed of 18 gauge zinc coated heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized and finished with a weather-resistant baked enamel finish. Units surface shall be tested 500 hours in salt spray test. Units shall have removable end panels which allow access to all major components and controls.

Refrigeration System — Single Compressor

TWA090A, TWA120A units shall have a single refrigeration circuit. Each refrigeration circuit has an integral subcooling circuit. A refrigeration filter drier, expansion valve and check valves shall be provided as standard.

The TWA090A, TWA120A units shall have both a liquid line and suction gas line service valve with gauge port. TWA090A, TWA120A units shall have one direct drive Trane hermetic scroll compressor with centrifugal oil pump providing positive lubrication to moving parts.

Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Crankcase heater, internal temperature and current-sensitive motor overloads shall be included for maximum protection. Scroll type compressor shall provide inherently low

vibration and noise by having no suction and discharge valves. External high and low pressure cutout devices shall be provided. Evaporator defrost control provided in indoor blower coil unit shall prevent compressor slugging by temporarily interrupting compressor operation when low evaporator coil temperatures are encountered.

Refrigeration System — Dual Compressor

TWA180B, TWA240B units shall have two separate and independent refrigeration circuits. Each refrigeration circuit shall have an integral subcooling circuit. A refrigeration filter drier shall be provided as standard.

Units shall have both a liquid line and suction gas line service valve with gauge ports. TWA180B, TWA240B units shall have two Trane direct drive hermetic scroll compressors with centrifugal oil pump and provide positive lubrication to all moving parts.

Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Crankcase heater, internal temperature and current-sensitive motor overloads shall be included for maximum protection. Scroll type compressor shall provide inherently low vibration and noise by having no suction and discharge valves.

External high and low pressure cutout devices shall be provided. Evaporator defrost control provided in indoor blower coil shall prevent compressor slugging by temporarily interrupting compressor operation when low evaporator coil temperatures are encountered.

Condenser Coil

Coils shall be internally finned or smooth bore 3/8" copper tubes mechanically bonded to configured aluminum plate fin as standard. Coil shall be factory pressure and leak tested to 420 psig air pressure. Metal grilles with PVC coating for coil protection is optional.

Condenser Fan and Motor(s)

Direct-drive, statically and dynamically balanced 26 or 28 inch propeller fan(s) with aluminum blades and electro-coated steel hubs shall be used in draw-through vertical discharge position. Either permanently lubricated totally enclosed or open construction type motors shall be provided and shall have built in current and thermal overload protection. Motor(s) shall have either ball or sleeve bearing type.

Controls

Heat pump units shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Control wiring shall be 24-volt control circuit which includes fusing and control transformer. Units shall provide external location for mounting a fused disconnect device. Time delay timers to prevent compressors in dual compressor units from simultaneous start-up and anti-recycle timers are available as optional accessories.

Defrost Controls

Electronic timed initiated, temperature terminated defrost system with choice of 50, 70, or 90 minute cycle. Timed override limits defrost cycle to 10 minutes.

Low Ambient Operation

Standard units shall start and operate to approximately 50°F when matched with Trane air handlers and coils. Optional head pressure control accessory permits operation to 0°F.

Accessories

Low Ambient Head Pressure Control — Shall modulate the RPM of unit outdoor fan motor in response to outdoor ambient temperatures and liquid line temperature. Accessory provides unit cooling operation to outdoor temperatures of 0°F.

Vibration Isolation Packages — Shall reduce transmission of noise

60

SSP-PRC001-EN

Page 60
Image 60
Trane SSP-PRC001-EN manual Mechanical Specifications

SSP-PRC001-EN specifications

The Trane SSP-PRC001-EN is a state-of-the-art product designed to enhance the efficiency and performance of HVAC systems. As a part of Trane’s expanding suite of smart building technologies, this device integrates advanced features and cutting-edge technology to provide optimal climate control for various applications, including commercial and industrial settings.

One of the primary features of the SSP-PRC001-EN is its ability to monitor and manage energy consumption effectively. The device employs real-time data analytics to provide insights into energy use patterns, allowing facility managers to make informed decisions that can significantly reduce operational costs. By leveraging this information, organizations can optimize their HVAC operations, leading to enhanced sustainability and compliance with environmental regulations.

Another notable characteristic of the SSP-PRC001-EN is its integration with Trane’s smart building technology. The system is designed to seamlessly connect with various sensors and building management systems, creating a comprehensive ecosystem for energy management. Its compatibility with existing infrastructure means that users can upgrade their systems without the need for extensive retrofitting, minimizing disruption while maximizing efficiency.

The SSP-PRC001-EN also boasts user-friendly interfaces that simplify operation and monitoring. Facility managers can easily access data and analytics through intuitive dashboards, which can be customized to display the most relevant information. This ease of use is critical for timely decision-making, especially in environments where rapid response to changing conditions is essential.

In terms of reliability and performance, the SSP-PRC001-EN is built to withstand demanding conditions. Designed with durability in mind, its rugged construction ensures long-lasting service, making it an ideal choice for facilities operating in various environments. Moreover, the system is engineered for flexibility, allowing for adjustments based on specific operational needs.

Overall, the Trane SSP-PRC001-EN combines advanced technology with practical features to deliver an efficient, reliable, and user-friendly solution for HVAC management. Whether for upgrading existing systems or integrating into new buildings, it stands as a testament to Trane's commitment to innovation and sustainability in the realm of climate control solutions. This product exemplifies how technological advancements can contribute to smarter building management and energy efficiency in today's demanding operational landscapes.