Trane SSP-PRC001-EN manual Electrical Data, Unit Wiring Heat Pumps, Fla Lra

Models: SSP-PRC001-EN

1 64
Download 64 pages 63.31 Kb
Page 32
Image 32

Electrical Data

Table 33.

Unit Wiring - Heat Pumps

 

 

 

 

 

Unit Operating Voltage

Minimum Circuit

Maximum Fuse Size or

 

 

Maximum Circuit

Tons

Unit Model No.

Range

Ampacity

Breaker(i)

 

TWA090A3

187-253

34.5

50

TWA090A4

414-506

18.1

25

 

TWA090AW

518-632

14.5

20

 

 

 

 

 

 

TWA120A3

187-253

48.1

70

10

TWA120A4

414-506

23.3

35

 

TWA120AW

518-632

18.8

25

 

 

 

 

 

 

TWA180B3

187-253

62.7

80

15

TWA180B4

414-506

32.9

45

 

TWA180BW

518-632

26.3

35

 

 

 

 

 

 

TWA240B3

187-253

87.8

100

20

TWA240B4

414-506

42.5

50

 

TWA240BW

518-632

34.2

45

(i)HACR type circuit breaker per NEC.

Table 34. Electrical Characteristics - Compressor and Condenser Fan Motors - 60 Cycle - Heat Pumps

 

 

 

Compressor Fan Motor

 

 

 

Condenser Fan Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Amps

 

 

 

 

Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLA

LRA

 

 

 

 

FLA

LRA

Tons

Unit Model No.

No.

Volts

Phase

(ea.)

(ea.)

 

No.

Volts

Phase

(ea.)

(ea.)

 

 

 

 

 

 

 

 

 

 

 

 

 

TWA090A3

1

208-230

3

25.1

182

1

208-230

1

3.1

8.1

TWA090A4

1

460

3

13.2

94.9

1

460

1

1.6

3.7

 

TWA090AW

1

575

3

10.6

70

1

575

1

1.2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

TWA120A3

1

208-230

3

33.7

278

1

208-230

1

6

17

10

TWA120A4

1

460

3

16.5

124

1

460

1

2.7

7

 

TWA120AW

1

575

3

13.4

92

1

575

1

2

5.7

 

 

 

 

 

 

 

 

 

 

 

 

 

TWA180B3

2

208-230

3

25.1

182

2

208-230

1

3.1

8.1

15

TWA180B4

2

460

3

13.2

94.9

2

460

1

1.6

3.7

 

TWA180BW

2

575

3

10.6

70

2

575

1

1.2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

TWA240B3

2

208-230

3

33.7

278

2

208-230

1

6

17

20

TWA240B4

2

460

3

16.5

124

2

460

1

2.7

7

 

TWA240BW

2

575

3

13.4

92

2

575

1

2

5.7

 

 

 

 

 

 

 

 

 

 

 

 

 

32

SSP-PRC001-EN

Page 32
Image 32
Trane SSP-PRC001-EN manual Electrical Data, Unit Wiring Heat Pumps, Compressor Fan Motor Condenser Fan Motor Amps, Fla Lra