Trane SSP-PRC001-EN manual Capacity Curves 20 Tons TWA240B Heat Pump Only

Models: SSP-PRC001-EN

1 64
Download 64 pages 63.31 Kb
Page 19
Image 19

Performance Data

20 Tons Gross Cooling Capacities and Capacity Curves

Table 10.

Gross Cooling Capacities (MBh) 20 Tons TWA240B Heat Pump Only

 

 

 

 

 

 

Suction Temperature (°F)

 

 

Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (°F)

30

35

40

45

50

55

 

 

 

 

 

 

 

 

 

Head press PSIG

183

190

196

203

211

219

65

Cap. Btuh/1000

217.4

237.4

258.4

280.5

303.5

327.5

 

Unit kW

16.09

16.51

16.96

17.44

17.96

18.5

 

 

 

 

 

 

 

 

 

Head press PSIG

209

216

223

231

239

248

75

Cap. Btuh/1000

206.8

226

246.3

267.6

290

313.3

 

Unit kW

17.58

18.05

18.56

19.11

19.68

20.28

 

 

 

 

 

 

 

 

 

Head press PSIG

238

245

253

261

270

279

85

Cap. Btuh/1000

196

214.4

233.9

254.5

276

298.3

 

Unit kW

19.35

19.88

20.44

21.03

21.65

22.27

 

 

 

 

 

 

 

 

 

Head press PSIG

269

277

285

294

303

313

95

Cap. Btuh/1000

185

202.6

221.3

240.9

261.4

282.6

 

Unit kW

21.39

21.97

22.57

23.2

23.83

24.47

 

 

 

 

 

 

 

 

 

Head press PSIG

304

312

320

329

339

349

105

Cap. Btuh/1000

173.8

190.6

208.4

227.1

246.5

266.5

 

Unit kW

23.68

24.31

24.95

25.6

26.24

26.87

 

 

 

 

 

 

 

 

 

Head press PSIG

341

349

358

368

378

388

115

Cap. Btuh/1000

162.4

178.5

195.4

213

231.2

249.9

 

Unit kW

26.23

26.89

27.56

28.22

28.86

29.46

Notes:

1.Performance data calculated at 15°F subcooling and 20°F superheat and does not include capacity loss due to refrigerant lines.

Figure 11. Capacity Curves 20 Tons TWA240B Heat Pump Only

SSP-PRC001-EN

19

Page 19
Image 19
Trane SSP-PRC001-EN manual Capacity Curves 20 Tons TWA240B Heat Pump Only