BACnet Object Properties

This section lists ranges, enumerations, and values for the set of Communicating Thermostat objects.

Fan Coil Object Properties

Table 6. List of property value range restrictions

 

Object Type and

Minimum Range

Maximum Range

 

Object Name

Instance

Value

Value

Default Value

Room Temperature

AV 7

-39.9°F (-40°C)

121.9°F (50°C)

N/A

 

 

 

 

 

Outdoor Temperature

AV 9

-39°F (-40°C)

121.9°F (50°C)

N/A

 

 

 

 

 

Room Humidity

AV 10

5%

90%

N/A

 

 

 

 

 

Supply Temperature

AI 12

-39.9°F (-40°C)

121.9°F (50°C)

N/A

 

 

 

 

 

PI Heating demand

AV 21

0%

100%

0%

 

 

 

 

 

PI Cooling demand

AV 22

0%

100%

0%

 

 

 

 

 

Occupied Heat

AV 39

40°F (4.5°C)

90°F (32°C)

72°F (22°C)

Setpoint

 

 

 

 

 

 

 

 

 

Occupied Cool

AV 40

54°F (12°C)

100°F (37.5°C)

74°F (24°C)

Setpoint

 

 

 

 

 

 

 

 

 

Stand-by Heat

AV 41

40°F (4.5°C)

90°F (32°C)

72°F (22°C)

Setpoint

 

 

 

 

 

 

 

 

 

Stand-by Cool

AV 42

54°F (12°C)

100°F (37.5°C)

74°F (24°C)

Setpoint

 

 

 

 

 

 

 

 

 

Unoccupied Heat

AV 43

40°F (4.5°C)

90°F (32°C)

62°F (16.5°C)

Setpoint

 

 

 

 

 

 

 

 

 

Unoccupied Cool

AV 44

54°F (12°C)

100°F (37.5°C)

80°F (26.5°C)

Setpoint

 

 

 

 

 

 

 

 

 

Password Value

AV 56

0

1000

0

 

 

 

 

 

Heating Setpoint Limit

AV 58

40°F (4.5°C)

90°F (32°C)

90°F (32°C)

 

 

 

 

 

Cooling Setpoint Limit

AV 59

54°F (12°C)

100°F (37.5°C)

54°F (12°C)

 

 

 

 

 

Deadband

AV 63

2°F (1°C)

5°F (2.5°C)

2°F (1°C)

 

 

 

 

 

Stand-by Time

AV 67

0.5 Hours

24.0 Hours

0.5 Hours

 

 

 

 

 

Unoccupied Time

AV 68

0.0 Hours

24.0 Hours

0.0 Hours

 

 

 

 

 

RH Setpoint

AV 45

30%

100%

50%

 

 

 

 

 

Dehumidification

AV 46

2%

20%

5%

Hysterisys

 

 

 

 

 

 

 

 

 

Dehumidification MAX

AV 47

20%

100%

100%

cooling

 

 

 

 

 

 

 

 

 

Table 7. List of property enumeration sets for BV objects and BI objects

 

Object Type and

 

 

 

Object Name

instance

Inactive_Text

Active_Text

Default value

Room Temp Override

BV 8

Normal

Override

Normal

 

 

 

 

 

Room Humidity

BV 11

Normal

Override

Normal

Override

 

 

 

 

 

 

 

 

 

Dehumidification

BV 13

Disabled

Enabled

Enabled

Lockout

 

 

 

 

 

 

 

 

 

AUX Command

BV 14

Off

On

Off

 

 

 

 

 

Dehumidification

BI 23

Off

On

Off

Status

 

 

 

 

 

 

 

 

 

Aux Status

BI 25

Off

On

Off

 

 

 

 

 

BI 1 Status

BI 29

Deactivated

Activated

Deactivated

 

 

 

 

 

BI 2 Status

BI 30

Deactivated

Activated

Deactivated

 

 

 

 

 

UI 3 Status(*)

BI 31

Deactivated

Activated

Deactivated

 

 

 

 

 

Local Motion

BI 32

No Motion

Motion

No Motion

 

 

 

 

 

Window Alarm

BI 35

Off

On

Off

 

 

 

 

 

14

BAS-SVP10A-EN

Page 14
Image 14
Trane BAS-SVP10A-EN manual BACnet Object Properties, Fan Coil Object Properties, List of property value range restrictions

BAS-SVP10A-EN, Trane Communicating Thermostats (BACnet) specifications

The Trane BAS-SVP10A-EN is a part of the Trane Communicating Thermostats series designed to facilitate efficient and effective building temperature control in HVAC systems. These thermostats work with BACnet (Building Automation and Control Network), a widely adopted communication protocol in building automation for networked control of HVAC systems, lighting, access control, and fire systems.

One of the standout features of the Trane BAS-SVP10A-EN is its compatibility with various Trane equipment and other BACnet-compliant devices. This versatility allows for seamless integration into existing building systems, enhancing operational efficiency. The thermostat is designed to support zoning applications, offering precise temperature control to individual areas or rooms, thus significantly improving occupant comfort while also minimizing energy consumption.

The Trane communicating thermostat is built with advanced technologies that ensure optimal performance. It utilizes digital communication, enabling real-time data exchange between the thermostat and the HVAC system. This capability enhances the responsiveness of the HVAC system, allowing it to adjust more accurately to changing environmental conditions. The thermostat features an intuitive interface with a clear display, making it user-friendly for building occupants and facility managers alike.

Another important characteristic is its advanced scheduling capabilities. Users can program customized heating and cooling schedules, promoting energy savings while maintaining comfort levels. Additionally, its remote access feature allows for monitoring and control from smartphones, tablets, or computers, making it convenient for users to manage their HVAC systems from virtually anywhere.

The Trane BAS-SVP10A-EN also boasts robust diagnostic and reporting functions. It can provide feedback on system performance, enabling proactive maintenance and troubleshooting, which increases the reliability of HVAC operations. Overall, the Trane Communicating Thermostat represents a sophisticated solution for modern building management, focusing on comfort, energy efficiency, and ease of integration into existing systems. With its commitment to leveraging cutting-edge technology, Trane continues to lead in providing innovative solutions for heating, ventilation, and air conditioning needs in diverse building environments.