BACnet Object Properties
This section lists ranges, enumerations, and values for the set of Communicating Thermostat objects.
Fan Coil Object Properties
Table 6. List of property value range restrictions
| Object Type and | Minimum Range | Maximum Range |
| |
Object Name | Instance | Value | Value | Default Value | |
Room Temperature | AV 7 | 121.9°F (50°C) | N/A | ||
|
|
|
|
| |
Outdoor Temperature | AV 9 | 121.9°F (50°C) | N/A | ||
|
|
|
|
| |
Room Humidity | AV 10 | 5% | 90% | N/A | |
|
|
|
|
| |
Supply Temperature | AI 12 | 121.9°F (50°C) | N/A | ||
|
|
|
|
| |
PI Heating demand | AV 21 | 0% | 100% | 0% | |
|
|
|
|
| |
PI Cooling demand | AV 22 | 0% | 100% | 0% | |
|
|
|
|
| |
Occupied Heat | AV 39 | 40°F (4.5°C) | 90°F (32°C) | 72°F (22°C) | |
Setpoint | |||||
|
|
|
| ||
|
|
|
|
| |
Occupied Cool | AV 40 | 54°F (12°C) | 100°F (37.5°C) | 74°F (24°C) | |
Setpoint | |||||
|
|
|
| ||
|
|
|
|
| |
AV 41 | 40°F (4.5°C) | 90°F (32°C) | 72°F (22°C) | ||
Setpoint | |||||
|
|
|
| ||
|
|
|
|
| |
AV 42 | 54°F (12°C) | 100°F (37.5°C) | 74°F (24°C) | ||
Setpoint | |||||
|
|
|
| ||
|
|
|
|
| |
Unoccupied Heat | AV 43 | 40°F (4.5°C) | 90°F (32°C) | 62°F (16.5°C) | |
Setpoint | |||||
|
|
|
| ||
|
|
|
|
| |
Unoccupied Cool | AV 44 | 54°F (12°C) | 100°F (37.5°C) | 80°F (26.5°C) | |
Setpoint | |||||
|
|
|
| ||
|
|
|
|
| |
Password Value | AV 56 | 0 | 1000 | 0 | |
|
|
|
|
| |
Heating Setpoint Limit | AV 58 | 40°F (4.5°C) | 90°F (32°C) | 90°F (32°C) | |
|
|
|
|
| |
Cooling Setpoint Limit | AV 59 | 54°F (12°C) | 100°F (37.5°C) | 54°F (12°C) | |
|
|
|
|
| |
Deadband | AV 63 | 2°F (1°C) | 5°F (2.5°C) | 2°F (1°C) | |
|
|
|
|
| |
AV 67 | 0.5 Hours | 24.0 Hours | 0.5 Hours | ||
|
|
|
|
| |
Unoccupied Time | AV 68 | 0.0 Hours | 24.0 Hours | 0.0 Hours | |
|
|
|
|
| |
RH Setpoint | AV 45 | 30% | 100% | 50% | |
|
|
|
|
| |
Dehumidification | AV 46 | 2% | 20% | 5% | |
Hysterisys | |||||
|
|
|
| ||
|
|
|
|
| |
Dehumidification MAX | AV 47 | 20% | 100% | 100% | |
cooling | |||||
|
|
|
| ||
|
|
|
|
|
Table 7. List of property enumeration sets for BV objects and BI objects
| Object Type and |
|
|
| |
Object Name | instance | Inactive_Text | Active_Text | Default value | |
Room Temp Override | BV 8 | Normal | Override | Normal | |
|
|
|
|
| |
Room Humidity | BV 11 | Normal | Override | Normal | |
Override | |||||
|
|
|
| ||
|
|
|
|
| |
Dehumidification | BV 13 | Disabled | Enabled | Enabled | |
Lockout | |||||
|
|
|
| ||
|
|
|
|
| |
AUX Command | BV 14 | Off | On | Off | |
|
|
|
|
| |
Dehumidification | BI 23 | Off | On | Off | |
Status | |||||
|
|
|
| ||
|
|
|
|
| |
Aux Status | BI 25 | Off | On | Off | |
|
|
|
|
| |
BI 1 Status | BI 29 | Deactivated | Activated | Deactivated | |
|
|
|
|
| |
BI 2 Status | BI 30 | Deactivated | Activated | Deactivated | |
|
|
|
|
| |
UI 3 Status(*) | BI 31 | Deactivated | Activated | Deactivated | |
|
|
|
|
| |
Local Motion | BI 32 | No Motion | Motion | No Motion | |
|
|
|
|
| |
Window Alarm | BI 35 | Off | On | Off | |
|
|
|
|
|
14 |