Trane BAS-SVP10A-EN BACnet Object Properties, Object Name, Object Type, Default Value, ActiveText

Models: BAS-SVP10A-EN Trane Communicating Thermostats (BACnet)

1 48
Download 48 pages 18.64 Kb
Page 20
Image 20
Table 15. List of property enumeration sets for BI and BV objects

BACnet Object Properties

Table 14. List of property value range restrictions for AI and AV objects (continued)

Object Name

Humidifier Output

Object Type

Under Range

and Instance

Value

AV 101

0%

 

 

Over Range Value

100%

Default Value

N/A

Table 15. List of property enumeration sets for BI and BV objects

 

Object Type

 

 

 

Object Name

and Instance

Inactive_Text

Active_Text

Default Value

Room Temp Override

BV 8

Normal

Override

Normal

 

 

 

 

 

Outdoor Temp Override

BV 10

Normal

Override

Normal

 

 

 

 

 

AUX

BI 24

Off

On

Off

 

 

 

 

 

G Fan

BI 25

Off

On

Off

 

 

 

 

 

Y1 Cool

BI 26

Off

On

Off

 

 

 

 

 

Y2 Cool

BI 27

Off

On

Off

 

 

 

 

 

W1 Heat

BI 28

Off

On

Off

 

 

 

 

 

W2 Heat

BI 29

Off

On

Off

 

 

 

 

 

Reversing Valve

BI 30

Off

On

Off

 

 

 

 

 

DI 1 Status

BI 31

Not Activated

Activated

Not Activated

 

 

 

 

 

DI 2 Status

BI 32

Not Activated

Activated

Not Activated

 

 

 

 

 

Local Motion

BI 33

No Motion

Motion

No Motion

 

 

 

 

 

Frost Alarm

BI 36

Off

On

Off

 

 

 

 

 

Clock Alarm

BI 37

Off

On

Off

 

 

 

 

 

Filter Alarm

BI 38

Off

On

Off

 

 

 

 

 

Service Alarm

BI 39

Off

On

Off

 

 

 

 

 

Fan Lock Alarm

BI 40

Off

On

Off

 

 

 

 

 

Temperature Scale

BV 47

°C

°F

°F

 

 

 

 

 

Frost Protection

BV 55

Off

On

Off

 

 

 

 

 

Aux Contact

BV 56

N.O.

N.C.

N.O.

 

 

 

 

 

Menu Scroll

BV 57

No Scroll

Scroll Active

Scroll Active

 

 

 

 

 

Fan Control

BV 62

Off

On

On

 

 

 

 

 

Fan Purge Delay

BV 64

Off

On

Off

 

 

 

 

 

Progressive Recovery

BV 70

Off

Active

Off

 

 

 

 

 

Mechanical Cooling Enabled

BV 79

Off

On

Off

 

 

 

 

 

Comfort Mode

BV 84

Comfort

Economy

Comfort

 

 

 

 

 

Reversing Valve

BV 85

Normally Cool

Normally Heat

Normally Heat

Energized in

Energized in

Configuration

Energized in Heating

 

Cooling

Cooling

 

 

 

 

 

 

 

 

Compressor Interlock

BV 86

Off

On

Off

 

 

 

 

 

RH Display

BV 88

Disabled

Enabled

Disabled

 

 

 

 

 

Dehumidification Lockout

BV 92

Disabled

Enabled

Enabled

Functions

 

 

 

 

 

 

 

 

 

Dehumidification Output

BI 93

Off

On

N/A

Status

 

 

 

 

 

 

 

 

 

20

BAS-SVP10A-EN

Page 20
Image 20
Trane BAS-SVP10A-EN manual BACnet Object Properties, List of property enumeration sets for BI and BV objects, Object Name