Trane Communicating Thermostat Points List
Table 44. Points Available in the TStat_Fan_Coil_Trane Template (continued)
|
|
|
| Data |
| TStat Device Point | Point | Point | Normaliza- |
Tracer SC Point Name | Name | Type | Instance | tion |
| Cooling Valve Status | MV | 27 |
|
|
|
|
|
|
| BI 1 Configuration | MV | 46 |
|
|
|
|
|
|
| BI 2 Configuration | MV | 47 |
|
|
|
|
|
|
| UI 3 Configuration | MV | 48 |
|
|
|
|
|
|
| Pipe Number | MV | 52 |
|
|
|
|
|
|
| AUX Configuration | MV | 54 |
|
|
|
|
|
|
| Fan Mode Sequence | MV | 57 |
|
|
|
|
|
|
| Proportional Band | MV | 65 |
|
|
|
|
|
|
| Floating Motor Timing | MV | 76 |
|
|
|
|
|
|
| On Off Control CPH | MV | 77 |
|
|
|
|
|
|
TStat_HeatPump_Trane Template
Table 45. Points Available in the TStat_HeatPump_Trane Template
|
|
|
| Data |
| TStat Device Point |
| Point | Normaliza- |
Tracer SC Point Name | Name | Point Type | Instance | tion |
Cool Output 1 Status | Y1 Cool | BI | 26 |
|
|
|
|
|
|
Cool Output 2 Status | Y2 Cool | BI | 27 |
|
|
|
|
|
|
Diagnostic Present | Service Alarm | BI | 39 |
|
|
|
|
|
|
Dirty Filter Alarm | Filter Alarm | BI | 38 |
|
|
|
|
|
|
Discharge Air Temperature | Supply Temperature | AI | 16 |
|
|
|
|
|
|
Display Temperature Scale | Temperature Scale | BV | 47 |
|
|
|
|
|
|
Fan Mode BAS | Fan Mode | MV | 15 |
|
|
|
|
|
|
Fan Output Status | G Fan | BI | 25 |
|
|
|
|
|
|
Heat Cool Mode Request | System Mode HP | MV | 13 | Yes |
|
|
|
|
|
Heat Output 1 Status | W1 Heat | BI | 28 |
|
|
|
|
|
|
In Defrost | Frost Protection | BV | 55 |
|
|
|
|
|
|
Keypad Lockout | Keypad Lockout | MV | 18 |
|
|
|
|
|
|
Low Temperature Alarm | Frost Alarm | BI | 36 |
|
|
|
|
|
|
Minimum Heating Cooling Setpoint | Deadband | AV | 52 |
|
Differential |
| |||
|
|
|
| |
|
|
|
|
|
Occupancy Input | Local Motion | BI | 33 |
|
|
|
|
|
|
Occupancy Request | Occupancy Command | MV | 12 | Yes |
|
|
|
|
|
Occupancy Status | Effective Occupancy | MV | 34 | Yes |
|
|
|
|
|
Occupied Cooling Setpoint | Occupied Cool Setpoint | AV | 43 |
|
|
|
|
|
|
Occupied Heating Setpoint | Occupied Heat Setpoint | AV | 42 |
|
|
|
|
|
|
Outdoor Air Temperature | Outdoor Temperature | AV | 9 |
|
|
|
|
|
|
Reversing Valve | Reversing Valve | BI | 30 |
|
|
|
|
|
|
Space Temperature Active | Room Temperature | AV | 7 |
|
|
|
|
|
|
Supply Fan Configuration Command | Fan Control | BV | 62 |
|
|
|
|
|
|
Supply Fan Failure | Fan Lockout Alarm | BI | 40 |
|
|
|
|
|
|
Timed Override Duration Setpoint | Temporary Occupancy Time | MV | 61 |
|
|
|
|
|
|
Unoccupied Cooling Setpoint | Unoccupied Cool Setpoint | AV | 45 |
|
|
|
|
|
|
Unoccupied Heating Setpoint | Unoccupied Heat Setpoint | AV | 44 |
|
|
|
|
|
|
| PI Heating Demand | AV | 20 |
|
|
|
|
|
|
| PI Cooling Demand | AV | 21 |
|
|
|
|
|
|
| Heating Setpoint Limit | AV | 48 |
|
|
|
|
|
|
| Cooling Setpoint Limit | AV | 49 |
|
|
|
|
|
|
43 |