Data Normalization
Tracer SC Point name: Occupancy Request
BACnet point name, type, and instance: Occupancy Command (MV 12)
Table 40. Tracer SC writing to the rooftop unit (Occupancy Request)
| Tracer SC state and text |
| Rooftop unit state and text |
1 | - Occupied | 2 | - Occupied |
2 | - Unoccupied | 3 | - Unoccupied |
3 | - Occupied Bypass | 2 | - Occupied |
4 | - Occupied Standby | 2 | - Occupied |
5 | - Auto | 1 | - Local Occupancy |
Table 41. Reading from rooftop unit to Tracer SC (Occupancy Request)
| Rooftop unit state and text |
| Tracer SC state and text |
1 | - Local Occupancy | 5 | - Auto |
2 | - Occupied | 1 | - Occupied |
3 | - Unoccupied | 2 | - Unoccupied |
Tracer SC Point name: Heat Cool Mode Request
BACnet point name, type and instance: System Mode (MV 14)
Table 42. Tracer SC writing to the rooftop unit (Heat Cool Mode Request)
|
| Tracer SC state and text |
| Rooftop unit state and text |
1 | - Auto | 2 | - Auto | |
2 | - Heat | 4 | - Heat | |
3 | - Morning | 4 | - Heat | |
4 | - Cool | 3 | - Cool | |
5 | - Night Purge | 3 | - Cool | |
6 | - Pre Cool | 3 | - Cool | |
7 | - Off | 1 | - Off | |
8 | - Test | 2 | - Auto | |
9 | - Emergency Heat | 4 | - Heat | |
10 | - Fan Only | 2 | - Auto | |
11 | - Free Cool | 3 | - Cool | |
12 | - | 3 | - Cool | |
13 | - Max Heat | 4 | - Heat | |
14 | - Economizer | 3 | - Cool | |
15 | - Dehumidify | 3 | - Cool | |
16 | - Calibrate | 2 | - Auto |
Table 43. Reading from rooftop unit to Tracer SC (Heat Cool Mode Request)
| Rooftop unit state and text |
| Tracer SC state and text |
1 | - Off | 7 | - Off |
2 | - Auto | 1 | - Auto |
3 | - Cool | 4 | - Cool |
4 | - Heat | 2 | - Heat |