Table 40. Tracer SC writing to the rooftop unit (Occupancy Request)

Data Normalization

Tracer SC Point name: Occupancy Request

BACnet point name, type, and instance: Occupancy Command (MV 12)

Table 40. Tracer SC writing to the rooftop unit (Occupancy Request)

 

Tracer SC state and text

 

Rooftop unit state and text

1

- Occupied

2

- Occupied

2

- Unoccupied

3

- Unoccupied

3

- Occupied Bypass

2

- Occupied

4

- Occupied Standby

2

- Occupied

5

- Auto

1

- Local Occupancy

Table 41. Reading from rooftop unit to Tracer SC (Occupancy Request)

 

Rooftop unit state and text

 

Tracer SC state and text

1

- Local Occupancy

5

- Auto

2

- Occupied

1

- Occupied

3

- Unoccupied

2

- Unoccupied

Tracer SC Point name: Heat Cool Mode Request

BACnet point name, type and instance: System Mode (MV 14)

Table 42. Tracer SC writing to the rooftop unit (Heat Cool Mode Request)

 

 

Tracer SC state and text

 

Rooftop unit state and text

1

- Auto

2

- Auto

2

- Heat

4

- Heat

3

- Morning Warm-up

4

- Heat

4

- Cool

3

- Cool

5

- Night Purge

3

- Cool

6

- Pre Cool

3

- Cool

7

- Off

1

- Off

8

- Test

2

- Auto

9

- Emergency Heat

4

- Heat

10

- Fan Only

2

- Auto

11

- Free Cool

3

- Cool

12

- Ice-Making

3

- Cool

13

- Max Heat

4

- Heat

14

- Economizer

3

- Cool

15

- Dehumidify

3

- Cool

16

- Calibrate

2

- Auto

Table 43. Reading from rooftop unit to Tracer SC (Heat Cool Mode Request)

 

Rooftop unit state and text

 

Tracer SC state and text

1

- Off

7

- Off

2

- Auto

1

- Auto

3

- Cool

4

- Cool

4

- Heat

2

- Heat