Additional Information and Considerations

Figure 6. Area members page (actions > edit configuration)

Heat only/cool only

If the thermostat is configured as cool only, it will not accept its Heat Cool Mode Request to be controlled to any heating mode. The converse applies if the thermostat is configured for heat only, it will not accept its Heat Cool Mode Request to be controlled to any cooling mode. If the point is controlled to an invalid state, it will quickly revert to the previous state.

Parameters not supported

In the Occupancy frame of the Equipment/Space status page, the following properties will not be displayed:

Last Controlled

Controlled by

Time Remaining

These are parameters that the thermostat points do not support.