8

Momentarilypressthe“SELECT”buttononthefrontpaneltobrowsethroughdifferentpowerreadings ontheLCDDisplay.

BYPASS OUTPUT
R: XXXV R: XXX.XV
S: XXXV S: XXX.XV
T: XXXV T: XXX.XV
(Bypass&OutputVoltage)
OUTPUT LOAD
R: XXX% XXX.XA
S: XXX% XXX.XA
T: XXX% XXX.XA
(OutputLoad&Current)
MAINS INVERTER
R: XXXV R: XXX.XV
S: XXXV S: XXX.XV
T: XXXV T: XXX.XV
(Mains&Inverter Voltage)
BYPASS: XX.XHz
MAINS: XX.XHz
OUTPUT: XX.XHz
INVERTER: XX.XHz
(Bypass,Mains,Output&InverterFrequency)
(ChargerMode,Charger/BatteryVoltage&BatteryPercentage)
(SerialNumber,DCBUSVoltage,Temperature&FirmwareVersion)
(ButtonFunctions)
CHARGE FLOATING
CHARGER:XXX.XV
BATTERY: XXX.XV
BATTERY: XXX.X%
SN: XXX
DCBUS: XXV - XXV
TEMP: XXX.X˚C
VERSION: XXX
ON: UPS START
OFF: UPSBYPASS
SEL: UPS MESSAGE
ENT: SET UPS
Press"SELECT"Button
Press"SELECT"Button
Press"SELECT"Button
Press"SELECT"Button
Press"SELECT"Button
Press"SELECT"Button
Press"SELECT"Button

WhileinBypassMode,theUPSmonitorstheinputvoltage,whichon Bypassequalstheoutputvoltage.Iftheoutputvoltagepassesoutofan acceptable

range(between15%higherand20%lowerthannominal),theUPSdisplaysthe conditiononitsLCDandstopssupplyingoutputpowertoitsload. If

powerlevelsreturntoanacceptablelevel,theUPSresumessupplyingpowertotheload,andits LCDreportsthatoutputvoltagewastoohighortoolow

atonetime,buthasreturnedtonominal.

Bypass Voltage Condition LCD Display Message

>15%HigherthanNominal BYPASSHINOO/P

>20% Lower than Nominal BYPASSLONOO/P

WasTooHigh,NowNominal BYPASSWASHI

WasTooLow,NowNominal BYPASSWASLO

4.4 LCD Display Select Button

5.1 Operation On Bypass—Voltage Out Of Range

5. Operation (Special Conditions)
4. Operation (Normal Conditions) (continued)