4.Operation (Normal Conditions) (continued)
4.4LCD Display Select Button
Momentarily press the “SELECT” button on the front panel to browse through different power readings on the LCD Display.
BYPASS OUTPUT
R:XXXV R: XXX.XV
S:XXXV S: XXX.XV
T:XXXV T: XXX.XV
(Bypass & Output Voltage)
Press "SELECT" Button
OUTPUT | LOAD |
R: XXX% | XXX.XA |
S: XXX% | XXX.XA |
T: XXX% | XXX.XA |
(Output Load & Current)
Press "SELECT" Button
MAINS | INVERTER |
R: XXXV | R: XXX.XV |
S: XXXV | S: XXX.XV |
T: XXXV | T: XXX.XV |
(Mains & Inverter Voltage)
Press "SELECT" Button
BYPASS: XX.X Hz
MAINS: XX.X Hz
OUTPUT: XX.X Hz
INVERTER: XX.X Hz
(Bypass, Mains, Output & Inverter Frequency)
Press "SELECT" Button
CHARGE FLOATING
CHARGER: XXX.XV
BATTERY: XXX.XV
BATTERY: XXX.X%
(Charger Mode, Charger/Battery Voltage & Battery Percentage)
Press "SELECT" Button
SN: | XXX |
DC BUS: | XXV - XXV |
TEMP: | XXX.X˚C |
VERSION: | XXX |
(Serial Number, DC BUS Voltage, Temperature & Firmware Version)
|
| Press "SELECT" Button | |
|
|
|
|
ON: | UPS START |
| |
OFF: | UPS BYPASS | (Button Functions) | |
SEL: | UPS MESSAGE | ||
ENT: | SET UPS |
|
Press "SELECT" Button
5.Operation (Special Conditions)
5.1Operation On Bypass—Voltage Out Of Range
While in Bypass Mode, the UPS monitors the input voltage, which on Bypass equals the output voltage. If the output voltage passes out of an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying output power to its load. If power levels return to an acceptable level, the UPS resumes supplying power to the load, and its LCD reports that output voltage was too high or too low at one time, but has returned to nominal.
Bypass Voltage Condition
LCD Display Message
>15% Higher than Nominal | BYPASS HI NO O/P |
|
|
>20% Lower than Nominal | BYPASS LO NO O/P |
|
|
Was Too High, Now Nominal | BYPASS WAS HI |
|
|
Was Too Low, Now Nominal | BYPASS WAS LO |
|
|
8