9. Specifications (continued)
Model: SU30K3/3
Input
Input Voltage | 120/208V AC, 3ø, 4 Wire (plus ground), wye |
|
|
Input Frequency | 60 Hz ± 3 Hz |
Voltage Correction Range | |
|
|
Input Current (Per Phase, | 90A |
Inrush Current | <300A |
Power Factor (Full Load) | >0.95 |
|
|
Efficiency (Full | >89% |
Circuit Breaker | 100A (3p) |
|
|
Input Bypass Circuit Breaker | 100A (3p) |
|
|
Output |
|
|
|
VA | 30000 |
Watts (Power Factor: 0.8) | 24000 |
|
|
Waveform | Sinewave |
|
|
Waveform | Sinewave |
Output Voltage (RMS) | 120/208V AC, 3ø, 4 Wire (plus ground), wye |
|
|
Output Frequency | 60 Hz (± 0.1 Hz on battery) |
|
|
Voltage Regulation | ±2% |
Max. Harmonic Distortion | <5% |
| |
Overload Capabilities | 102% (continuous), 102%~125% (1 min.), |
| 125%~150% (30 sec.), 150% (2 sec.) |
Short Circuit Capability | 250A |
|
|
Crest Factor | 3:1 |
Battery |
|
Battery Type | Sealed, Lead Acid, 240V DC, 9AH |
|
|
Battery Pack Quantity | Three Packs (20 12V DC Batteries per pack) |
|
|
Protection | Six |
| fuses (two per battery pack) and fuse block |
| (1 per battery pack) |
Typical Backup Time (Half Load) | 13 min. + |
|
|
Typical Backup Time (Full Load) | 5 min. + |
Operation |
|
0 ms | |
(Line to Battery, Battery to Line) |
|
Audible Noise (Full Load @ 1 meter) | <65 dBA |
|
|
Indicators |
|
Includes an LCD Display and LEDs (AC Line In, Bypass Line In, AC to DC, DC to AC, AC Output, Battery
Communications
Includes an
Connections
Input Terminal Block | 100A |
Output Terminal Block | 100A |
Physical Specifications |
|
Unit Dimensions (H x W x D) | 35.3 x 19.3 x 36 in. |
|
|
Unit Weight | 662 lb. |
Shipping Dimensions (H x W x D) | 43 x 28 x 44.5 in. |
|
|
Shipping Weight | 750 lb. |
|
|
Model: SU30K3/3XR5
Input
Input Voltage | 120/208V AC, 3ø, 4 Wire (plus ground), wye |
|
|
Input Frequency | 60 Hz ± 3 Hz |
|
|
Voltage Correction Range | |
Input Current (Per Phase, | 90A |
|
|
Inrush Current | <300A |
|
|
Power Factor (Full Load) | >0.95 |
Efficiency (Full | >89% |
|
|
Circuit Breaker | 100A (3p) |
|
|
Input Bypass Circuit Breaker | 100A (3p) |
Output |
|
VA | 30000 |
|
|
Watts (Power Factor: 0.8) | 24000 |
Waveform | Sinewave |
Waveform | Sinewave |
|
|
Output Voltage (RMS) | 120/208V AC, 3ø, 4 Wire (plus ground), wye |
Output Frequency | 60 Hz (± 0.1 Hz on battery) |
|
|
Voltage Regulation | ±2% |
|
|
Max. Harmonic Distortion | <5% |
| |
Overload Capabilities | 102% (continuous), 102%~125% (1 min.), |
| 125%~150% (30 sec.), 150% (2 sec.) |
Short Circuit Capability | 250A |
Crest Factor | 3:1 |
|
|
Battery |
|
|
|
Battery Type | Sealed, Lead Acid, 240V DC, 9AH |
Battery Pack Quantity | Five Packs (20 12V DC Batteries per pack) |
Protection | Ten |
| fuses (two per battery pack) and fuse block |
| (1 per battery pack) |
Typical Backup Time (Half Load) | 25 min. + |
|
|
Typical Backup Time (Full Load) | 11 min. + |
|
|
Operation |
|
|
|
0 ms | |
(Line to Battery, Battery to Line) |
|
Audible Noise (Full Load @ 1 meter) | <65 dBA |
Indicators |
|
Includes an LCD Display and LEDs (AC Line In, Bypass Line In, AC to DC, DC to AC, AC Output, Battery
Communications
Includes an
Connections
Input Terminal Block | 100A |
|
|
Output Terminal Block | 100A |
|
|
Physical Specifications |
|
|
|
Unit Dimensions (H x W x D) | 48.5 x 19.3 x 36 in. |
Unit Weight | 935 lb. |
|
|
Shipping Dimensions (H x W x D) | 61.5 x 31 x 44.5 |
|
|
Shipping Weight | 1152 lb. |
+ Backup times are expandable with additional Battery Packs, sold separately. The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.
1111 W. 35th Street • Chicago, IL 60609 USA
(773)
200901138
18