7
WIRING CONNECTION
Connectyourwiringtotheinputandoutputterminalblockslocatedon therearpanelofyourUPS(seefigurebelow).
CAUTION!
Qualified personnel should follow all procedures prescribed by N.E.C. and other local
codes for hardwiring devices to a utility source.
Ensure that cables are fitted with cable sleeves and are secured by connector clamps.
Tighten connections with a torque of not less than 35 inch-pounds. Observe the
appropriate cable connection regulations [e.g. National Electrical Code (NEC) in the
U.S.] at all times. Using cables of improper size may damage your equipment and cause
fire hazards.
Note: When shipped from the factory, bypass input and main input wires are connected.
•Press thefront“OFF”button.Yourloadwillstillbeenergized.Theinverterisnowoff,butyourUPSisnotfullydeactivated.TheLCDDisplay
 willshow“ONBYPASS.”
•TurntheMain InputSwitchandBypassInputSwitchCircuitBreakersOFF.Yourloadwillnolongerbeenergized,andtheLCDdisplaywillbedark.
 NOTE:IftheUPSSystemremainsoffforanextendedperiodoftime,itshould beturnedbackonperiodicallytoallowtheinternalbatteriesto
 recharge.TheUPSSystemshouldbeturnedonandtheinternalbatteriesshould berechargedatleastoneuninterrupted24-hourperiodevery
 3months.Failuretoprovideperiodicrechargetimemaycauseirreversiblebatterydamage.
•Make suretheUPSisproperlyinstalled(seesection3,Installation)and theManualBypassSwitchissettoNORMAL.
•TurntheACMainInputSwitch andBypassInputSwitchCircuitBreakersON.
•If yourACinputisprovidingpowernormallywithinyourselectedrange,yourconnectedloadwillenergizein Bypass.However,theUPS'sinverter
 isnotyeton.Pressthefront“ON”buttontobegininverteroperation.
•If yourACinputisnotprovidingpowernormally,youhavetheoptionofstartingfrombattery.(Yourbatterymustbeatleastpartiallychargedfor
thisoperationtosucceed.)Pressandholdboththe"BatteryStart"switch andthe“ON”buttonforthreesecondstostartyourUPS in“ONBATTERY”
 mode.Notethatsomeelectronicequipmentmaydrawmoreampsduringstartup; whenstartingfrombattery,considerreducingtheinitialloadon
the UPS.
•The UPSwillperformabriefself-testandshowtheresultsonthe LCDDisplay.(Seesection4.3,Self-Testingfordisplaysequence.)Aftera 
 successfulself-test,theUPSwillprovideACpowerfromtheinvertertoyourload.
WhenyouturntheUPSON,itwillperformabriefself-test. Seechartsbelowfordisplaysequences.
DisplaysequencewhenACinputpowerispresent: DisplaysequencewhenACinputpowerisabsent:
(possibleonlywiththe"BatteryStart"Switch)
SELFTESTING... SELFTESTING...
RECTIFIEROK BATTERYOK
CHARGEROK DCTODCOK
BATTERYOK INVERTER TEST
DCTODCOK
INVERTER TEST

4.1 Turning the UPS On

4.2 Turning the UPS Off

4.3 Self-Testing

3.5 Initial Battery Charging

3.4 UPS Input And Output Hardwire Connection (continued)
4. Operation (Normal Conditions)
3. Installation (continued)
Althoughtheinternalbatteriesarechargedpriortoshipping,allowtheinternalbatteries tochargeuninterruptedfor24hoursafterinitialinstallation.