Specifications (continued)

Model: SU30K3/3

Input

Input Voltage

120/208V AC, 3ø, 4 Wire (plus ground), wye

Input Frequency

60 Hz ± 3 Hz

Voltage Correction Range

88-144/166-250V AC

Input Current (Per Phase, On-Line)

90A

Inrush Current

<300A

Power Factor (Full Load)

>0.95

Efficiency (Full Load/On-Line)

>89%

Circuit Breaker

200A (3p)

Input Bypass Circuit Breaker

200A (3p)

 

 

Output

 

VA

30000

Watts (Power Factor: 0.8)

24000

Waveform (On-Line)

Sinewave

Waveform (On-Battery)

Sinewave

Output Voltage (RMS)

120/208V AC, 3ø, 4 Wire (plus ground), wye

Output Frequency

60 Hz (± 0.1 Hz on battery)

Voltage Regulation

±2%

Max. Harmonic Distortion

 

(Non-Linear Full Load)

<5%

Overload Capabilities

<102% (continuous), 102%~125% (1 min.),

 

125%~150% (30 sec.), >150% (2 sec.)

Short Circuit Capability

>250A

Crest Factor

3:1

 

 

Battery

 

Battery Type

Sealed, Lead Acid, 240V DC, 9AH

Battery Pack Quantity

Three Packs (20 12V DC Batteries per pack)

Protection

Six UL-recognized 30A 600VDC rated

 

cartridge fuses (two per battery pack) and

 

fuse block (1 per battery pack)

Typical Backup Time (Half Load) 13 min. +

Typical Backup Time (Full Load) 5 min. +

Operation

On-Line Transfer Time

(Line to Battery, Battery to Line) 0 ms

Audible Noise (Full Load @ 1 meter) <65 dBA

Indicators

Includes an LCD Display and LEDs (AC Line In, Bypass Line In, AC to DC, DC to AC, AC Output, Battery Back-Up, Bypass).

Communications

Includes an RS-232 DB9 female connector, an AS-400 DB9 female connector, a dry contact DB9 female connector and an accessory slot.

Connections

Input Terminal Block

100A

Output Terminal Block

100A

 

 

Physical Specifications

 

Unit Dimensions (H x W x D)

35.3 x 19.3 x 36 in.

Unit Weight

662 lb.

Shipping Dimensions (H xW x D) 43 x 28 x 44.5 in.

Shipping Weight

750 lb.

Model: SU30K3/3XR5

Input

Input Voltage

120/208V AC, 3ø, 4 Wire (plus ground), wye

Input Frequency

60 Hz ± 3 Hz

Voltage Correction Range

88-144/166-250V AC

Input Current (Per Phase, On-Line)

90A

Inrush Current

<300A

Power Factor (Full Load)

>0.95

Efficiency (Full Load/On-Line)

>89%

Circuit Breaker

200A (3p)

Input Bypass Circuit Breaker

200A (3p)

 

 

Output

 

VA

30000

Watts (Power Factor: 0.8)

24000

Waveform (On-Line)

Sinewave

Waveform (On-Battery)

Sinewave

Output Voltage (RMS)

120/208V AC, 3ø, 4 Wire (plus ground), wye

Output Frequency

60 Hz (± 0.1 Hz on battery)

Voltage Regulation

±2%

Max. Harmonic Distortion

 

(Non-Linear Full Load)

<5%

Overload Capabilities

<102% (continuous), 102%~125% (1 min.),

 

125%~150% (30 sec.), >150% (2 sec.)

Short Circuit Capability

>250A

Crest Factor

3:1

 

 

Battery

 

Battery Type

Sealed, Lead Acid, 240V DC, 9AH

Battery Pack Quantity

Five Packs (20 12V DC Batteries per pack)

Protection

Ten UL-recognized 30A 600VDC rated

 

cartridge fuses (two per battery pack) and

 

fuse block (1 per battery pack)

Typical Backup Time (Half Load) 25 min. +

Typical Backup Time (Full Load) 11 min. +

Operation

On-Line Transfer Time

(Line to Battery, Battery to Line) 0 ms

Audible Noise (Full Load @ 1 meter) <65 dBA

Indicators

Includes an LCD Display and LEDs (AC Line In, Bypass Line In, AC to DC, DC to AC, AC Output, Battery Back-Up, Bypass).

Communications

Includes an RS-232 DB9 female connector, an AS-400 DB9 female connector, a dry contact DB9 female connector and an accessory slot.

Connections

Input Terminal Block

100A

Output Terminal Block

100A

 

 

Physical Specifications

 

Unit Dimensions (H x W x D)

48.5 x 19.3 x 36 in.

Unit Weight

935 lb.

Shipping Dimensions (H xW x D) 61.5 x 31 x 44.5 in.

Shipping Weight

1152 lb.

+ Backup times are expandable with additional Battery Packs, sold separately. The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.

Regulatory Compliance Identification Numbers

For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marking name or model number of the product.

FCC Specifications for Models with FCC Approval:

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. The user must use shielded cables and connectors with this product. Any changes or modifications to this product not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.

18

Page 18
Image 18
Tripp Lite 3-Phase 20kVA, 30kVA owner manual Model SU30K3/3XR5