Tripp Lite 30kVA Inverter on Warnings, Operation Under Shutdown, Switching UPS to Bypass Mode

Models: 3-Phase 20kVA 30kVA

1 56
Download 56 pages 1.82 Kb
Page 9
Image 9

Operation (Special Conditions) (continued)

INVERTER ON WARNINGS

When the inverter is ON, the LCD Display may show any one of the following warnings:

Condition

LCD Display Message

 

 

UPS Output Overload

OVERLOAD 110%

 

 

UPS Charger Failure

CHARGER FAILURE

 

 

Abnormal Input Frequency

FREQUENCY ERROR

 

 

Abnormal Input Phase

PHASE ABNORMAL!

 

 

Battery is Depleting*

ON BATTERY

 

 

Battery Charge is Nearly Depleted*

BATTERY LOW

 

 

* During a prolonged blackout, users should save files and shut down connected equipment.

The “BATTERY LOW” message indicates the UPS's batteries are nearly out of power and UPS shut down is imminent.

OPERATION UNDER SHUTDOWN

Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: For all conditions, the “Input,” “Output” and “Bypass” LEDs will be illuminated.

Condition

LCD Display Message

 

 

Overload Shutdown

ON BYPASS

 

OVERLOAD 150%

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

UPS Output Short Circuit

ON BYPASS

 

SHORT CIRCUIT!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Overtemperature

ON BYPASS

 

HIGH TEMP!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

DC BUS Overvoltage

ON BYPASS

 

DC BUS O.V.P.!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

DC BUS Failure

ON BYPASS

 

DC BUS FAIL!

 

SHUTDOWN...

 

VERSION: XXXXXXX

Condition

LCD Display Message

 

 

R/S/T Inverter Output Failure

ON BYPASS

 

R OUTPUT FAIL!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Low Battery

BYPS OFF NO O/P

 

LOW BATTERY!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Remote Shutdown

BYPS OFF NO O/P

 

REMOTE SHUTDOWN

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Emergency Stop

BYPS OFF NO O/P

 

EMERGENCY STOP!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

OPERATION OF MANUAL BYPASS SWITCH

Turn this switch to “BYPASS” before performing any maintenance on the UPS with the connected load supported. Connected equipment will receive filtered AC mains power, but will not receive battery power in the event of a blackout.

SWITCHING UPS TO “BYPASS” MODE

Press the “OFF” button.

Turn the “Manual Bypass” Switch clockwise from NORMAL to BYPASS.

Turn the Main Input Switch Circuit Breaker OFF.

SWITCHING UPS TO “NORMAL” MODE

Turn the Main Input Switch Circuit Breaker ON.

Turn the “Manual Bypass” Switch counterclockwise from BYPASS back to NORMAL.

Press the “ON” button.

9

Page 9
Image 9
Tripp Lite 30kVA, 3-Phase 20kVA Inverter on Warnings, Operation Under Shutdown, Operation of Manual Bypass Switch