Tripp Lite 350, 525 owner manual Basic Operation, Buttons Front Panel

Models: 525 350

1 41
Download 41 pages 47.39 Kb
Page 8
Image 8

200310077 93-2200 Sinewave SmartPro Rackmount UPS Owner’s Manual.qxd 10/21/2003

3:32 PM Page 7

Basic Operation

Buttons (Front Panel)

“POWER” Button

To turn the UPS ON: with the UPS plugged into a live AC wall outlet*, press and hold the POWER button for one second.** Release the button. If utility power is absent, you can “cold-start” the UPS (i.e.: turn it ON and supply power for a limited time from its batteries***) by pressing and holding the POWER button for one second.**

To turn the UPS OFF: with the UPS ON and receiving utility power, press and hold the POWER button for one second.** Then unplug the UPS from the wall outlet. The UPS will be completely OFF.

*After you plug the UPS into a live AC outlet, the UPS will automatically charge its batteries, but will not supply power to its outlets until it is turned ON. ** The alarm will beep once briefly after the indi- cated interval has passed. *** If fully charged.

“MUTE/TEST” Button

To Silence (or “Mute”) UPS Alarms: briefly press and release the MUTE/TEST button.*

To Run a Self-Test: with your UPS plugged in and turned ON, press and hold the MUTE/TEST button for two seconds.* Continue holding the button until the alarm beeps several times and the UPS performs a self test. See “Results of a Self-Test” below. Note: you can leave connected equipment on during a self-test. Your UPS, however, will not perform a self-test if you have placed it in “Standby/Charge-Only” mode (see “POWER” Button description).

CAUTION! Do not unplug your UPS to test its batteries. This will remove safe electrical grounding and may introduce a damaging surge into your network connections.

Results of a Self-Test: The test will last approximately 10 seconds as the UPS switches to battery to test its load capacity and battery charge. All LEDs will be lit and the UPS alarm will sound.

If the “OUTPUT LOAD LEVEL” LED remains lit red and the alarm contin- ues to sound after the test, the UPS’s outlets are overloaded. To clear the over- load, unplug some of your equipment and run the self-test repeatedly until the “OUTPUT LOAD LEVEL” LED is no longer lit red and the alarm is no longer sounding.

CAUTION! Any overload that is not corrected by the user immediately following a self-test may cause the UPS to shut down and cease supplying output power in the event of a blackout or brownout.

If the “BATTERY WARNING” LED remains lit and the alarm continues to sound after the test, the UPS batteries need to be recharged or replaced. Allow the UPS to recharge continuously for 12 hours, and repeat the self-test. If the LED remains lit, contact Tripp Lite for service. If your UPS requires battery replacement, visit www.tripplite.com/ support/battery/index.cfm to locate the specific Tripp Lite replacement battery for your UPS.

* The alarm will beep once briefly after the indicated interval has passed.

7

Page 8
Image 8
Tripp Lite 350, 525 owner manual Basic Operation, Buttons Front Panel