Operation (continued)
Resetting Your Inverter/Charger to Restore AC Power
Your Inverter/Charger may cease supplying AC power or DC charging power in order to protect itself from overload or to protect your elec- trical system. To restore normal functioning:
Overload Reset: Switch operating mode switch to “OFF” and remove some of the connected electrical load (ie: turn off some of the AC devices drawing power which may have caused the overload of the unit). Wait one minute, then switch operating mode switch back to either “AUTO/REMOTE” or “CHARGE ONLY.”
Configuration
Set Configuration DIP Switches
Using a small tool, set the Configuration DIP Switches (located on the front panel, see diagram) to optimize Inverter/Charger operation depending on your application. Refer to the appropriate section to review the instructions for your specific model.
B4 | B3 | B2 | B1 |
Group B Dip Switches (Not on 612 Models)
INPUT C/B
A4 | A3 | A2 | A1 |
| OUTPUT C/B 12A |
|
Group A Dip Switches (All Models)
Group A DIP Switches (All Models)
Using a small tool, configure your Inverter/Charger by setting the four Group A DIP Switches (located on the front panel of your unit; see diagram) as follows:
| A1 | Select Battery |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| |||
| A4 | A3 |
| A2 |
| A1 |
|
|
| |||||
|
| (All models) |
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| CAUTION: The Battery Type DIP Switch setting must |
|
|
|
|
|
|
|
|
| ||||
| match the type of batteries you connect, or your batteries |
|
|
|
|
|
|
|
|
| ||||
| may be degraded or damaged over an extended period of |
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| ||||||
| time. See “Battery Selection,” p. 7 for more information. |
|
|
|
|
|
|
|
|
| ||||
| Battery Type | Switch Position |
|
|
|
| ||||||||
| Gel Cell (Sealed) Battery | Up |
|
|
|
|
|
|
|
| ||||
| Wet Cell (Vented) Battery | Down (factory setting) |
A2 | Select ChargerEnable/Inhibit |
|
|
|
|
|
|
|
|
|
|
A4 |
| A3 |
| A2 |
| A1 | INHIBIT | ||||
| (750 and 1250 models only) |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| |
| Switch is preset to ENABLE, which |
|
|
|
|
|
|
|
|
|
|
| permits continuous battery charging. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ENABLE | |||
| If you are connecting your unit to |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| |
| batteries with a separate charger, you may set this switch to | ||||||||||
| INHIBIT to disable its |
Battery Type | Switch Position |
Inhibit | Up |
Enable | Down (factory setting) |
A4 A3 Select Low AC Input Voltage Point for Switching to Battery—
OPTIONAL*
| Switch |
Voltage | Position |
105V | #A4 Up & #A3 Up |
95V | #A4 Up & #A3 Down |
85V | #A4 Down & #A3 Up |
75V | #A4 Down & #A3 Down |
| (factory setting) |
*Most of your connected appliances and equipment will perform adequately when your Inverter/Charger's Low AC Voltage Input Point (DIP Switch #3 and #4 of Group A) are set to 95V. However, if the unit frequently switches to battery power due to momentary low line voltage swings that would have little effect on equipment operation, you may wish to adjust this setting. By decreasing the Low AC Voltage Input Point, you will reduce the number of times that your unit switches to battery due to voltage swings.
A4 A3 A2 A1
A4 A3 A2 A1
A4 A3 A2 A1
A4 A3 A2 A1