Troubleshooting

Try these remedies for common APS problems before calling for help. Call Tripp Lite Customer Service at (773) 869-1234 before returning your APS for service.

SYMPTOM

PROBLEMS

CORRECTIONS

APS does not provide

APS not properly connected to

Connect APS to utility power.

AC output (AC input present)

utility power.

 

 

 

 

 

Circuit breaker is tripped.

Reset circuit breaker.

 

 

 

 

APS shutdown due to excessive

Turn APS “OFF”. Wait 1 minute and

 

battery voltage, indicating possible

switch to “AUTO/REMOTE”.

 

charger failure. Line disconnected

 

 

to prevent permanent battery

 

 

damage.

 

 

 

 

 

APS is overheated.

Check air circulation near vents.

 

 

 

 

APS is set to “OFF”

Set APS to “AUTO/REMOTE” or

 

 

“CHARGE-ONLY”.

 

 

 

APS does not provide

Operating Mode Switch is set

Set Operating Mode Switch to “AUTO/

AC output (AC input absent)

to “CHARGE ONLY”.

REMOTE.”

 

 

 

 

Load or High Temperature fault.

Turn APS “OFF”. Wait 1 minute.

 

 

Remove overload. Check that vents

 

 

are clear for air circulation. Switch

 

 

to “AUTO/REMOTE”.

 

 

 

 

Excessive battery discharge.

Check battery condition.

 

 

 

APS will not charge the

Connected batteries are dead.

Check and replace old batteries.

battery (AC input present)

(All Battery Indicator lights will be

 

 

flashing slowly.)

 

 

Battery fuse* is blown.

Check and replace fuse.

 

 

 

 

Battery cabling* is loose or degraded.

Check and tighten or replace cabling.

 

 

 

 

APS charger failure.

Turn APS “OFF”. Wait 1 minute and

 

 

switch to “AUTO/REMOTE”. If

 

 

automatic shutdown occurs, call

 

 

Tripp Lite Customer Service.

 

 

 

All APS Indicator Lights are

This is normal if the APS is set

OFF (AC input absent)

to “CHARGE-ONLY”

 

 

 

 

All APS Indicator Lights are

Excessive battery discharge.

Use an auxiliary charger* to raise

OFF (AC input is present or

 

battery voltage. Check external battery

absent)

 

connections and fuse. Automatically

 

 

resets when condition is cleared.

 

 

 

All APS Battery Indicator

Excessive battery discharge.

Use an auxiliary charger* to raise

Lights are slowly flashing.

 

battery voltage. Automatically resets

 

 

when condition is cleared.

 

 

 

APS “LOAD” Battery Light

Inverter shutdown because load

Turn APS “OFF”. Wait 1 minute.

flashing

is too high or temperature is too

Remove overload. Check that vents

 

high.

are clear for air circulation. Switch

 

 

to “AUTO/REMOTE”.

 

 

 

All APS Battery Lights are

High battery voltage shutdown

Check all charging sources. Reset by

rapidly flashing

during battery charging.

cycling control switch to "OFF" then to

 

 

“AUTO/REMOTE” or “CHARGE-ONLY”.

 

 

 

APS red “BATTERY HI/MED/LO”

Inverter shutting down due to low

Prepare for loss of power to

light is flashing

battery charge.

connected equipment.

*User supplied

12

Page 12
Image 12