Configuration
DIP Switches
Using a small tool, set the four “Battery Type / Voltage Point” Configuration DIP Switches (located on the front panel of your APS); see Diagram 4, p. 28.
• Select Battery Type (DIP Switch #1)
CAUTION:The Battery Type DIP Switch setting must match the type of batteries you connect or your batteries may be degraded or damaged over an extended period of time. See “Battery Selection,”page 6 for more information.
Battery Type | Switch Position |
Gel Cell (Sealed) Battery | Up |
Wet Cell (Vented) Battery | Down* |
• Select High AC Voltage Switch To
Battery Point (DIP Switch #2)
Voltage | Switch Position |
145V | Up |
135V | Down* |
4 | 3 | 2 | 1 | Gel Cell |
|
Wet Cell*
4 3 2 1 145V
135V*
• Select Low AC Voltage Switch To
Battery Point (DIP Switches #4 & #3)
Voltage | Switch Postion |
105V | #4 Up & #3 Up |
95V | #4 Up & #3 Down |
85V | #4 Down & #3 Up |
75V | #4 Down & #3 Down* |
Most loads will perform adequately when your APS’s High AC Voltage Point DIP Switch #2 is set to 135V and its Low AC Voltage Point DIP Switches #3 and #4 are set to 95V. However, if your APS frequently switches to battery power due to momentary high/low line voltage swings that would have little effect on equipment operation, you may wish to adjust these settings. Your APS will switch to battery due to voltage swings the least if the High AC Voltage Switch to Battery Point is on its highest setting and the Low AC Voltage Switch to Battery Point is on its lowest setting.
4 3 2 1
105V
4 3 2 1
95V
4 3 2 1
85V
4 3 2 1
75V*
* Factory default settings.