Configuration

Configuration

DIP Switches

Using a small tool, set the four “Battery Type / Voltage Point” Configuration DIP Switches (located on the front panel of your APS); see Diagram 4, p. 28.

• Select Battery Type (DIP Switch #1)

CAUTION:The Battery Type DIP Switch setting must match the type of batteries you connect or your batteries may be degraded or damaged over an extended period of time. See “Battery Selection,”page 6 for more information.

Battery Type

Switch Position

Gel Cell (Sealed) Battery

Up

Wet Cell (Vented) Battery

Down*

• Select High AC Voltage Switch To

Battery Point (DIP Switch #2)

Voltage

Switch Position

145V

Up

135V

Down*

4

3

2

1

Gel Cell

 

Wet Cell*

4 3 2 1 145V

135V*

• Select Low AC Voltage Switch To

Battery Point (DIP Switches #4 & #3)

Voltage

Switch Postion

105V

#4 Up & #3 Up

95V

#4 Up & #3 Down

85V

#4 Down & #3 Up

75V

#4 Down & #3 Down*

Most loads will perform adequately when your APS’s High AC Voltage Point DIP Switch #2 is set to 135V and its Low AC Voltage Point DIP Switches #3 and #4 are set to 95V. However, if your APS frequently switches to battery power due to momentary high/low line voltage swings that would have little effect on equipment operation, you may wish to adjust these settings. Your APS will switch to battery due to voltage swings the least if the High AC Voltage Switch to Battery Point is on its highest setting and the Low AC Voltage Switch to Battery Point is on its lowest setting.

4 3 2 1

105V

4 3 2 1

95V

4 3 2 1

85V

4 3 2 1

75V*

* Factory default settings.