Basic Operation continued

Power Sensitivity Adjustment: This dial is normally set fully counter- clockwise, which enables the UPS to provide maximum protection against waveform distortions in its AC input. When such distortion occurs, the UPS will normally switch to providing sine wave power from its battery reserves for as long as the distortion is present. In areas with poor utility power or where the UPS’s input power comes from a backup generator, chronic waveform distortion could cause the UPS to switch to battery too frequently, draining its battery reserves. You may be able to reduce how often your UPS switches to battery due to moderate waveform distortion by experimenting with different settings for this dial. As the dial is turned clockwise, the UPS becomes more tolerant of variations in its input power’s AC waveform.

Note: The further the dial is adjusted clockwise, the greater the degree of waveform distortion the UPS will allow to pass to connected equipment. When experimenting with different settings for this dial, operate connected equipment in a safe test mode so that the effect on the equipment of any waveform distortions in the UPS’s output can be evaluated without disrupting critical operations.

Input Breakers: The SMART2500XLHG uses two input breakers to protect your electrical circuit from overcurrent draw from the UPS load. One breaker protects LINE, while the other NEUTRAL. If these breakers trip, remove some of the load and reset them by pressing the breakers in.

Guidance and Manufacturer’s Declaration

Product Information

AC Input Voltage

120V

Input Amp(s)

16A

No. of Phases

Single

Class Type

Class 1

Plug/Connector Type

IEC inlet C20

 

 

Operation

Continuous

 

 

AC Input Frequency

60Hz

AC Input Protection (Qty./Type/Rating)

Input breaker (2x 20A thermal)

Max AC Leakage Current (uA)

Less than 100uA

Weight

73.3 lbs (33.2 kg)

 

 

Contraindication

None

 

 

Guidance and Manufacturer’s Declaration—Electromagnetic Emissions

This Medical-Grade UPS is intended for use in the electromagnetic environment specified below. The customer or the user of this Medical-Grade UPS should assure that it is used in such an environment.

Emissions Test

Compliance

Electromagnetic Environment - Guidance

RF Emissions CISPR 11

Group 1

The Medical-Grade UPS uses RF energy only for its internal

 

 

function. Therefore, its RF emissions are very low and unlikely

 

 

to cause any interference in nearby electronic equipment.

RF Emissions CISPR 11

Class B

The Medical-Grade UPS is suitable for use in all

 

 

establishments other than domestic and those directly

 

 

connected to the public low-voltage power supply network

 

 

that supplies buildings used for domestic purposes.

 

 

 