Guidance and Manufacturer’s Declaration cont.
Guidance and Manufacturer’s
This
|
| Compliance | Electromagnetic |
Immunity Test | IEC 60601 Test Level | Level | Environment - Guidance |
Electrostatic Discharge (ESD) | + / - 6kV contact | Complies | Floors should be wood, |
IEC | + / - 8kV air |
| concrete or ceramic tile. If |
|
|
| colors are covered with |
|
|
| synthetic material, the |
|
|
| relative humidity should be |
|
|
| at least 30%. |
|
|
|
|
Electrical Fast Transient/Burst | + / - 2kV for power supply | Complies | Mains power quality should |
IEC | lines |
| be that of a typical |
| + / - 1kV for input/output |
| commercial or hospital |
| lines |
| environment. |
Surge | + / - 1kV differential mode | Complies | Mains power quality should |
IEC | + / - 2kV common mode |
| be that of a typical |
|
|
| commercial or hospital |
|
|
| environment. |
|
|
|
|
Voltage dips, short | <5% UT | Complies | Mains power quality should |
interruptions and voltage | (>95% dip in UT) for .5 cycle |
| be that of a typical |
variations on power supply | 40% UT |
| commercial or hospital |
input lines | (60% dip in UT) for 5 cycles |
| environment. |
IEC | 70% UT |
|
|
| (30% dip in UT) for 25 cycles |
|
|
| <5% UT |
|
|
| (>95% dip in UT) for 5 seconds |
|
|
Power Frequency (50/60 Hz) | 3 A/m | Complies | Power frequency magnetic |
Magnetic Field |
|
| fields should be at levels |
IEC |
|
| characteristic of a typical |
|
|
| location in a typical |
|
|
| commercial or hospital |
|
|
| environment. |
|
|
|
|
Note: UT is the AC mains voltage prior to application of the test level.
Overcurrent Protection
The unit is equipped with 2 20A,
Battery Pack
The unit comes with a 48VDC, rechargeable sealed
11