Basic Operation

Buttons (Front Panel)

“ON/OFF/STANDBY” Button

To turn the UPS ON: with the UPS plugged into a live AC wall outlet*, press and hold the “ON/OFF/STANDBY” button for one second.** Release the but- ton. If utility power is absent, you can “cold-start” the UPS (i.e.: turn it ON and supply power for a limited time from its batteries***) by pressing and holding the “ON/OFF/STANDBY” button for one second.**

To turn the UPS OFF: with the UPS ON and receiving utility power, press and hold the “ON/OFF/STANDBY” button for one second.** Then unplug the UPS from the wall outlet. The UPS will be completely OFF.

*After you plug the UPS into a live AC outlet, the UPS (in “Standby” mode) will automatically charge its batteries, but will not supply power to its outlets until it is turned ON. ** The alarm will beep once briefly after the indicated interval has passed. *** If fully charged.

“MUTE/TEST” Button

To Silence (or “Mute”) UPS Alarms: briefly press and release the MUTE/TEST button.

To Run a Self-Test: with your UPS plugged in and turned ON, press and hold the MUTE/TEST button for two seconds.* Continue holding the button until the alarm beeps several times and the UPS performs a self test. See “Results of a Self-Test” below. Note: you can leave connected equipment on during a self-test. Your UPS, however, will not perform a self-test if the UPS is not turned on (see “ON/OFF/STANDBY” Button description).

CAUTION! Do not unplug your UPS to test its batteries. This will remove safe electrical grounding and may introduce a damaging surge into your network connections.

Results of a Self-Test: the test will last approximately 10 seconds as the UPS switches to battery to test its load capacity and battery charge.

If the “OUTPUTLOAD LEVEL” LED remains lit red and the alarm continues to sound after the test, the UPS’s outlets are overloaded. To clear the overload, unplug some of your equipment and run the self-test repeatedly until the “OUTPUT LOAD LEVEL” LED is no longer lit red and the alarm is no longer sounding.

CAUTION! Any overload that is not corrected by the user immediately following a self-test may cause the UPS to shut down and cease supplying output power in the event of a blackout or brownout.

If the “BATTERY WARNING” LED remains lit and the alarm continues to sound after the test, the UPS batteries need to be recharged or replaced. Allow the UPS to recharge continuously for 12 hours, and repeat the self-test. If the LED remains lit, contact Tripp Lite for service. If your UPS requires battery replacement, visit www.tripplite.com to locate the specific Tripp Lite replacement battery for your UPS.

* The alarm will beep once briefly after the indicated interval has passed.

7

Page 7
Image 7
Tripp Lite SMX1500XLRT2U, SMX500RT1U, SMX3000XLRT2U, SMX1000RT2U, SMX750RT1U owner manual Basic Operation, Buttons Front Panel

SMX750RT1U, SMX1000RT2U, SMX1500XLRT2U, SMX3000XLRT2U, SMX500RT1U specifications

The Tripp Lite SMX500RT1U is a high-performance rack-mountable uninterruptible power supply (UPS) designed to protect critical equipment in server rooms and data centers. This compact unit provides reliable power backup and surge protection, ensuring that sensitive electronic devices remain operational during power outages or fluctuations.

One of the standout features of the SMX500RT1U is its 500VA/300W power capacity, which makes it suitable for protecting a variety of devices, including servers, network switches, and telecommunication equipment. The device offers sine wave output, which is essential for maintaining the integrity and reliability of powered equipment, particularly those with power-sensitive components.

The SMX500RT1U utilizes advanced battery technology, ensuring a dependable performance even under varying load conditions. Its internal batteries are designed for easy replacement, minimizing downtime and maintaining efficiency. The UPS also includes a smart charge technology, which optimizes charging time and extends battery life, ensuring that the unit is always ready to provide power when needed.

This model features six NEMA 5-15R output receptacles, allowing users to connect multiple devices while ensuring that they are protected from surges and brownouts. The unit also supports hot-swappable batteries, allowing for seamless battery replacement without interrupting the power supply to connected devices.

Another important characteristic of the SMX500RT1U is its versatility in management options. It comes equipped with USB and serial ports, enabling users to connect to their servers for monitoring and management. The included PowerAlert Software aids in providing detailed information on power conditions and allows for safe shutdowns in case of prolonged outages.

The Tripp Lite SMX500RT1U is designed with a form factor suitable for 1U rack installation, making it an excellent choice for space-constrained environments. Its efficient cooling design enhances performance while minimizing noise, making it ideal for use in any setting, from quieter network closets to bustling data centers.

In summary, the Tripp Lite SMX500RT1U is a robust UPS solution that offers essential features and technologies for users looking to protect their critical devices from power interruptions. Its reliable performance, ease of use, and compact design make it a valuable addition to any infrastructure in need of dependable power management.