BATTERY CHARGE WARNINGS

Since your UPS can provide battery backup only for as long as the batteries remain charged, these warnings should be acted on immediately.

Battery Charge Warning

LCD Display Message

Battery charge nearly depleted

BATTERY LOW

AC/DC charger not operating

CHARGER FAILURE!

OPERATION UNDER SHUTDOWN

Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: For all conditions, the “Input,” “Output” and “Bypass” LEDs will be illuminated.

Condition

LCD Display Message

Extended Overload (>150%)

OVERLOAD 150%

 

SHUT DOWN

Output Short Circuit

SHORT CIRCUIT!

 

SHUT DOWN

Remote Shutdown Command

REMOTE

(FROM DB9 INTERFACE)

SHUT DOWN

Remote Shutdown Command

EMERGENCY STOP!

(from RJ11 interface)

SHUT DOWN

 

 

Internal Faults

INVERTER TOO LO

 

SHUT DOWN

 

INVERTER TOO HI

 

SHUT DOWN

 

DC BUS +/- HIGH/LOW

 

SHUT DOWN

 

OVERTEMPERATURE

 

SHUT DOWN

 

 

OPERATION OF MANUAL BYPASS SWITCH

Turn this switch to “BY-

 

PASS” before performing

 

any maintenance on the

 

UPS

with the connected

AC INPUT

load supported. Connected

 

equipment

will

receive

 

filtered AC mains power,

 

but

will

not

receive

 

battery power in the event

 

of a blackout.

 

 

INPUT BREAKER

SUBP CHARGER OUTPUT

 

M AN UAL BYPAS S SW ITCH

 

OU TPUT BREAK ER

U P S

OUTPUT

 

UPS P OW ER

STD.SUBP CONNECTED MODELS CONTAIN SUBP CHARGER

BATTERYCURRENT IN THE AREA MARKED BY THE DASHED OUTLINE. ALL COMPONENTS ARE ELECTRONICALLY ISOLATED FROM THE AC LINE.

SWITCHING UPS TO “BYPASS” MODE

Turn the “ON/OFF” Switch OFF. (LCD will read "ON BYPASS.")

Turn the “Manual Bypass” Switch clockwise from NORMAL to BYPASS.

Turn the AC Input Circuit Breaker OFF.

Open battery fuse holders and remove the battery fuses from all battery packs and from all SU6K models.

SWITCHING UPS TO “NORMAL” MODE

Replace all battery fuses in the battery fuse holders and close the battery fuse holders.

Turn the AC Input Circuit Breaker ON.

Turn the “Manual Bypass” Switch counterclockwise from BYPASS back to NORMAL.

Turn the “ON/OFF” Switch ON.

12

Page 12
Image 12
Tripp Lite SU10K owner manual Battery Charge Warnings, Operation Under Shutdown, Operation of Manual Bypass Switch

SU10K specifications

The Tripp Lite SU10K is a powerful and reliable uninterruptible power supply (UPS) designed to protect critical equipment and ensure seamless operation during power interruptions. With a robust output of 10,000 VA, this UPS caters to various applications, from data centers to IT infrastructure, making it a versatile solution for businesses of all sizes.

One of the standout features of the SU10K is its line-interactive topology. This technology allows the UPS to correct voltage fluctuations without switching to battery mode, thereby extending battery life and providing a stable power supply to connected devices. This is particularly beneficial for equipment that is sensitive to power quality, such as servers, networking gear, and telecommunications systems.

The SU10K is equipped with a reliable battery system that ensures a continuous power supply during outages. Its hot-swappable batteries make maintenance convenient, allowing users to replace batteries without powering down connected equipment. This feature minimizes downtime, ensuring that critical systems remain operational at all times.

The unit offers a wide range of output options, allowing users to configure the UPS according to their specific needs. With multiple output receptacles, including both NEMA and IEC connectors, the SU10K can accommodate various devices, ensuring flexibility in the setup. The UPS also supports advanced power management features, including SNMP, allowing for remote management and monitoring through network integration. This capability enables IT administrators to keep a close eye on power usage and battery health and receive alerts about potential issues.

In addition to its technical features, the Tripp Lite SU10K boasts a compact design that enables easy installation in various environments. The unit is rack-mountable, making it suitable for traditional server racks or cabinet installations. Its design also incorporates advanced cooling technology, ensuring efficient heat dissipation during operation to enhance performance and extend equipment lifespan.

Furthermore, the SU10K's LCD display provides users with real-time information regarding power status, battery condition, and load capacity, facilitating quick assessments and decision-making. Overall, the Tripp Lite SU10K combines robust technology with user-friendly features, making it an excellent choice for safeguarding critical equipment and ensuring business continuity in the face of power challenges.