UPS LOCATION

Move your UPS over short distances using its wheels. Stabilize the UPS by releasing the stabilizers on each side of the unit. NOTE: Do not stack the UPS Systems or external battery packs.

INPUT AND OUTPUT CONNECTION

WIRING SELECTION

Choose appropriate cabling (depending on current carried; see chart below) to connect your UPS to an AC power supply and your equipment to your UPS:

MODEL

RATED INPUT

RATED OUTPUT

RATED OUTPUT

OUTPUT

 

CURRENT

CURRENT

CURRENT

PROTECTION

 

208/240 1Ø 3 Wire

120-208/240V 1Ø 3 Wire

120V 1Ø 3 Wire

CIRCUIT

SU6K

30A 8 AWG (8mm2/60oC)

30A 8 AWG (8mm2/60oC)

2 x 32A 6 AWG (14mm2/60oC)

32A

 

 

 

 

 

SU10K

50A 6 AWG (14mm2/60oC)

50A 6 AWG (14mm2/60oC)

2 x 50A 4 AWG (22mm2/60oC)

63A

WIRING CONNECTIONS

Connect your wiring to the input and output terminal blocks located on the lower rear panel of your UPS (see figure below). Before cable connection, turn the UPS OFF and pull out the fuse holder. Ensure the cable is fitted with a cable sleeve and is secured by a connector clamp. The minimum tightening torque is 35 lbs. per square inch. Connect the ground wire (typically colored green and yellow) to the terminal marked with the letter "G."

Cable Connection for 6kVA or 10kVA Output (6kVA shown)

CAUTION: Observe the appropriate cable connection regulations [e.g. National Electrical Code (NEC) in the U.S.] at all times. Using cables of improper size may damage your equipment and cause fire hazards. Ground the UPS and the load equipment as shown in the figure.

GROUND UPS

CONNECTION

TO THE BUILDING

EARTH

(GROUND)

LOAD 1

LOAD 2

LOAD 3

7