Tripp Lite SU10K owner manual Remote Emergency Power OFF, DRY Contact Interface Table

Models: SU10K

1 17
Download 17 pages 15.09 Kb
Page 14
Image 14

DRY CONTACT INTERFACE:

This female DB9 contact-closure port allows your UPS to send contact-closure signals to indicate that it is on battery back-up mode and if its batteries are running low. The port can also receive a remote shutdown signal.

Pin assignment:

Im in .> 3.3m A

L O W B A T T E R Y

B A C K -U P

 

 

 

N O

N O

C O M

N C

C O M N C

 

 

SIGNAL FROM

 

 

COMPUTER

REMOTE SHUTDOWN SIGNAL FROM EXTERNAL

>2 sec

MAXIMUM CAPACITY OF DRY CONTACT:

AC250V/3A

DC 30V/3A

12V

DRY CONTACT INTERFACE TABLE

UPS Operating

Pin 8,3

Pin 1,3

Mode

 

 

 

 

 

Normal

OPEN

OPEN

 

 

 

Back Up

CLOSE

*

 

 

 

Low Battery

CLOSE

CLOSE

 

 

 

* Inactive: may be in either state.

REMOTE EMERGENCY POWER OFF:

This RJ11 modular jack allows remote emergency shutdown.

Pin assignment (SU6K Shown)

1 2 V

X

1 K

X

ON LINE

MODE

ECONOMY

MODE

1

2

3

4

5

6

Pin 1

If there is a short between pins 2 and 3, 2 and 5, 4 and 5, or 3 and 4, the UPS will power off.

14

Page 14
Image 14