BATTERY CONDITION VERIFICATION

When the UPS is operating from battery power, the alarm and LCD Display will both alert you to the UPS battery’s charge condition.

Battery Charge Condition

Alarm

LCD Display

FULL

Short Beep (every 2 seconds)

ON BATTERY

 

 

BATT = XXV XX%

 

 

 

LOW

Short Beep (every 1/2 second)

BATTERY LOW

 

 

BATT = XXV XX%

UNDER

Continuous Beep

BATTERY UNDER

 

 

SHUT DOWN

 

 

 

INITIAL BATTERY CHARGING (OPTIONAL)

Your UPS System’s battery is fully charged prior to shipping. However, if your UPS has been stored for an extended period, recharge its battery for 8 hours. To charge, turn on the AC Input Breaker. The LCD Display will illuminate and indicate “ON BYPASS.” DO NOT turn on the AC Output Breaker to apply the load until the battery is fully charged. Once the UPS is in use, it will charge the batteries and maintain the charge level automatically.

Operation (Normal Conditions)

TURNING THE UPS ON

Make sure the UPS is properly installed (see Installation section) and the Manual Bypass Key is set to NORMAL.

Turn the AC Input Circuit Breaker ON, then turn the Output Circuit Breakers ON.

If your AC input is providing power normally within your selected range (see Input Voltage Selection, pg. 6, and Specs, pg. 17), your connected load will energize. However, the UPS's inverter is not yet on. Press the front "ON/OFF" switch ON to begin inverter operation.

If your AC input is not providing power normally, you have the option of starting from battery. (Your battery must be at least partially charged for this operation to succeed.) Press and hold both the "Battery Start" switch and the "ON/OFF" switch for three seconds to start your UPS in "ON BATTERY" mode. Note that some electronic equipment may draw more amps during startup; when starting from battery, consider reducing the initial load on the UPS.

The UPS will perform a brief self-test and show the results on the LCD Display. (See Self-Test section, pg. 10, for display sequence.) After a successful self-test, the UPS will provide AC power from the inverter to your load.

TURNING THE UPS OFF

Press the front “ON/OFF” Switch OFF. Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display will show “ON BYPASS."

Turn the AC Input and Output Circuit Breakers OFF. Your load will no longer be energized, and the LCD display will be dark.

9