True Manufacturing Company T-35 True Food Service Equipment, Inc, If The Compressor Will, Not Run

Models: T-35

1 24
Download 24 pages 13.36 Kb
Page 16
Image 16
IF THE COMPRESSOR WILL

True Food Service Equipment, Inc.

INSTALLATION / OPERATION INSTRUCTIONS

IF THE COMPRESSOR WILL

Make sure capacitors are discharged

5. If the compressor has an external

NOT RUN

 

before checking. Check for continuity

protector, check for continuity through

 

 

between each capacitor terminal and the

the protector or protectors. All external

1. If there is no voltage at the

 

compressor terminals, follow the

case. Continuity indicates a short, and

inherent protectors on compressors can

wiring diagram and check back from

the capacitor should be replaced.

be replaced in the field.

 

 

compressor to the power supply to find

Substitute a “known to be good” start

 

 

 

 

where the circuit is interrupted.

 

IF THE MOTOR COMPRESSOR

2. If power is available at the

 

capacitor if available. If compressor

STARTS BUT TRIPS

 

 

 

then starts and runs properly, replace

REPEATEDLY ON THE

 

 

compressor terminals, and the

 

the original start capacitor.

OVERLOAD PROTECTOR

 

 

compressor does not run, check the

 

 

 

 

 

If a capacitor tester is not available, an

1. Check the compressor suction

 

 

voltage at the compressor terminals

and discharge pressures while the

 

 

while attempting to start the

 

ohmmeter may be used to check run

compressor is operating. Be sure the

compressor.

 

and start capacitors for shorts or open

pressures are within the limitations

 

 

circuits. Use an ohmmeter set to its

of the compressor. If pressures are

If voltage at the compressor terminals is

highest resistance scale, and connect

excessive it may be necessary to clean

below 90% of the nameplate voltage, it

prods to capacitor terminals.

the condenser, purge air from the

 

 

is possible the motor may not develop

a) With a good capacitor, the

system, replace crankcase pressure

sufficient torque to start. Check to

indicator should first move zero, and

regulating valve.

 

 

determine if wire sizes are adequate,

then gradually increase to infinity.

 

 

 

 

electrical connections are loose, the

b) If there is no movement of the

An excessively low suction pressure

circuit is overloaded, or if the power

ohmmeter indicator, an open circuit is

may indicate a loss of charge.

 

 

supply is inadequate.

 

indicated.

 

 

 

 

 

 

c) If the ohmmeter indicator

On units with no service gauge parts

3. On single phase compressors,

moves to zero, and remains there or on

where pressures can be checked,

check

a defective capacitor or relay may

a low resistance reading, a short circuit

condenser to be sure it is clean and fan

prevent the compressor starting. If

is indicated. Defective capacitors

is running. Excessive temperatures on

the compressor attempts to start but

should be replaced.

suction and discharge line may also

is unable to do so, or if there is a

4. If the correct voltage is available

indicate abnormal operating conditions.

humming sound, check the relay to

 

 

 

 

see if the relay contacts are damaged

at the compressor terminals, and no

2. Check the line voltage at the motor

or fused. The relay points should be

current is drawn, remove all wires from

terminals while the compressor is

 

 

closed during the initial starting cycle,

the terminals and check for continuity

operating. The voltage should be

 

 

but should open as the compressor

through the motor windings. On single

within 10% of the nameplate voltage

comes up to speed.

 

phase motor compressors, check for

rating. If outside those limits, the

 

 

 

 

continuity from terminals C to R, and C

voltage supply must be brought

 

 

Remove the wires from the starting

to S. On compressors with line break

 

 

within the proper range, or a motor

relay and capacitors. Use a high

inherent protectors, an open overload

compressor with different electrical

voltage ohmmeter to check for

 

protector can cause a lack of continuity.

characteristics must be used.

 

 

continuity throughout the relay

 

If the compressor is warm, wait one

 

 

 

 

coil. Replace the relay if there is not

hour for the compressor to cool and

3. Check the amperage drawn while

continuity. Use an ohmmeter to check

recheck. If continuity cannot be

the compressor is operating. Under

across the relay contacts. Potential

established through all motor windings,

normal operating conditions, the

 

 

relay contacts are normally closed when

the compressor should be replaced.

amperage drawn will seldom exceed

the relay is not energized, current relay

Check the motor for ground by means

110% of the nameplate amperage.

contacts are normally open. If either

High amperage can be caused by low

gives an incorrect reading, replace the

of a continuity check between the

voltage, defective running capacitors,

relay.

 

common terminal and the compressor

or a defective starting relay.

 

 

 

 

shell. If there is a ground, replace the

 

 

Any capacitor found to be bulging,

compressor.

 

 

 

 

leaking, or damaged should be

 

 

Continued on next page

 

 

 

replaced.

 

 

 

 

 

 

 

 

 

 

14

............ www.truemfg.com

14

Page 16
Image 16
True Manufacturing Company T-35 True Food Service Equipment, Inc, Installation / Operation Instructions, Not Run