True Food Service Equipment, Inc.

INSTALLATION / OPERATION INSTRUCTIONS

 

 

Wire Gauge for 2% Voltage Drop in Supply Circuits

 

 

115 Volt

 

 

 

Distance in Feet to Center of Load.

 

 

 

Amps

20

30

40

50

60

70

80

90

100

120

140

160

 

2

14

14

14

14

14

14

14

14

14

14

14

14

3

14

14

14

14

14

14

14

14

14

14

14

12

4

14

14

14

14

14

14

14

14

14

12

12

12

5

14

14

14

14

14

14

14

12

12

12

10

10

6

14

14

14

14

14

14

12

12

12

10

10

10

7

14

14

14

14

14

12

12

12

10

10

10

8

8

14

14

14

14

12

12

12

10

10

10

8

8

9

14

14

14

12

12

12

10

10

10

8

8

8

10

14

14

14

12

12

10

10

10

10

8

8

8

12

14

14

12

12

10

10

10

8

8

8

8

6

14

14

14

12

10

10

10

8

8

8

6

6

6

16

14

12

12

10

10

8

8

8

8

6

6

6

18

14

12

10

10

8

8

8

8

8

8

8

5

20

14

12

10

10

8

8

8

6

6

6

5

5

25

12

10

10

8

8

6

6

6

6

5

4

4

30

12

10

8

8

6

6

6

6

5

4

4

3

35

10

10

8

6

6

6

5

5

4

4

3

2

40

10

8

8

6

6

5

5

4

4

3

2

2

45

10

8

6

6

6

5

4

4

3

3

2

1

50

10

8

6

6

5

4

4

3

3

2

1

1

 

 

 

Wire Gauge for 2% Voltage Drop in Supply Circuits

 

 

 

 

230 Volt

 

 

 

Distance in Feet to Center of Load.

 

 

 

 

 

Amps

20

30

40

50

60

70

80

90

100

120

140

160

 

 

 

 

 

5

14

14

14

14

14

14

14

14

14

14

14

14

 

 

6

14

14

14

14

14

14

14

14

14

14

14

12

 

 

7

14

14

14

14

14

14

14

14

14

14

12

12

 

 

8

14

14

14

14

14

14

14

14

14

12

12

12

 

 

9

14

14

14

14

14

14

14

14

12

12

12

10

 

 

10

14

14

14

14

14

14

14

12

12

13

10

10

 

 

12

14

14

14

14

14

14

12

12

12

10

10

10

 

 

14

14

14

14

14

14

12

12

12

10

10

10

8

 

 

16

14

14

14

14

12

12

12

10

10

10

8

8

 

 

18

14

14

14

12

12

12

10

10

10

8

8

8

 

 

20

14

14

14

12

10

10

10

10

10

8

8

8

 

 

25

14

14

12

12

10

10

10

10

8

8

6

6

 

 

30

14

12

12

10

10

10

8

8

8

6

6

6

 

 

35

14

12

10

10

10

8

8

8

8

6

6

5

 

 

40

14

12

10

10

8

8

8

6

6

6

5

5

 

 

50

12

10

10

8

6

6

6

6

6

5

4

4

 

 

60

12

10

8

6

6

6

6

6

5

4

4

3

 

 

70

10

10

8

6

6

6

5

5

5

4

2

2

 

 

80

10

8

8

6

6

5

5

4

4

3

2

2

 

 

90

10

8

6

6

5

5

4

4

3

3

1

1

 

 

100

10

8

6

6

5

4

4

3

3

2

1

1

 

5

 

 

 

............ www.truemfg.com

 

5

Page 7
Image 7
True Manufacturing Company TR2RRT-2S-2S, TR1RRI-1S installation manual Wire Gauge for 2% Voltage Drop in Supply Circuits