ELECTRONIC CONTROL INSTRUCTION

5-1-3. FUNCTION TABLE

No

Function

Controlled

Description

Part

 

 

 

ELECTRONIC CONTROL INSTRUCTION

Controlled

No FunctionDescription

Part

1.It can be set as below according to the connection of JUMPER (J1,J2,J3)in the main PCB.

 

 

1.

88 LED displays inside temperture

1

Initial

2.

Begin to run immediately on the higher than 50and

Operation

 

begin to run after 5 minutes pause on the lower

 

 

 

 

 

than 50.

1.The temperature can be changed by pushing up/down buttons.

2.88 LED displays inside temperture

3.Buzzer buzzes 1time whenever a button is pressed

4.Compressor automatically turns on and off by C-sensor (Except error mode)

2

Temperature

Compressor

5. Comp. on/off temperature ()

 

 

Control

LED

Setting

5.0

3.0

1.0

-1.0

-2.0

 

 

 

 

Comp On

5.3

3.5

0.8

-1.3

-1.8

 

 

 

Comp OFF

-2.5 -4.7 -7.4

-9.4

-10.6

 

 

 

--------------------------------------------------------

 

 

 

 

Setting

-3.0

-5.0

-7.0

-9.0

 

 

 

 

Comp On

-3.1

-4.9

-5.8

-7.6

 

 

 

 

Comp OFF

-11.2

-13.0

-13.9

-15.7

 

FREEZER /

REFRIGERATOR

4 MAIN PCB

DEFROST TIME

 

 

 

 

JUMPER

P. C . B

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1,2,3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JUMPER

JUMPER

CONNECTION

DISCONNECTI

REMARKS

NO.

FUNCTION

 

-ON

 

 

JP1

Unit of the

Indicated to

Indicated to

 

 

Temperature

Temperature

Temperature

 

 

 

 

 

 

JP2

Mode of the

 

 

 

 

control to

The controller

The controller

 

 

 

 

 

 

 

 

Refrigerator

of Freezer

of Refrigerator

 

 

 

 

/ Freezer

 

 

 

 

 

 

Control of

 

 

Applied to the

JP3

8 Hr

6 Hr

Freezer model

Defrost cycle

 

 

 

 

only.

 

 

 

 

 

 

1.Defrost Cycle : It can be set 8Hr or 6Hr by OPTION JUMPER (JP3)

ERROR CODE (FREEZER)

Code

Content

Perception Method

Refrigeration state

 

 

 

 

 

 

 

 

 

 

- short circuit

- Normal operation

 

 

 

JUMPER

TRANSFORMER

1,2,3

P. C . B

D-sensor

 

- Defrost

 

 

- wire disconnection

Heater ON : 20 MINUTES

cS

C-sensor

- short circuit

 

 

 

 

3

Defrost

Heater

Function

Compressor

 

2. The condition of DEFROST operation

-It runs regularly according to the defrost cycle with adding up the plug in time.

-When the defrost starting time comes, COMPRESSOR must be turned off and the defrost operation cycle begins to run according to the conditions as the below 1 and 2 after checking the temperature by

DEFROST SENSOR.

Cond ition 1(In case the temperature checked by DEFROST SENSOR is low than 23); Defrost Heater (Max. 40Min. running) runs by that time DEFROST-SENSOR sensor 53and COMPRESSOR runs after 10minutes pauses.

cO

 

- wire disconnection

- Time control

 

Comp ON : 10 MINUTES

cS

C-sensor

- short circuit

Comp OFF : 6 MINUTES

 

D-sensor

 

cO

- wire disconnection

 

18

19

Page 10
Image 10
Turbo Air MSF-23NM, MSR-23G-1, MSR-49N, MSR-49G-2, MSR-23NM, MSF-49NM manual Error Code Freezer, P. C . B

FAQ

How can I change the temperature of the Turbo Air door models?

The temperature can be changed by pushing up/down buttons, with 88 LED displays inside for temperature monitoring.

What should I do if the buzzer buzzes when pressing a button on the electronic control panel?

If the buzzer buzzes 1 time whenever a button is pressed, it is a normal function as per the instructions.

How does the compressor operate in the Turbo Air door models?

The compressor automatically turns on and off by C-sensor, except in error modes.