The top and bottom valve can never be open at the same time. After initial startup whichever compartment calls for cooling first, will have priority. Once the setpoint is achieved the other compartment will be cooled if necessary.
When both compartments have reached setpoint and the compressor shuts off, the last bypass valve that was open will remain open for four minutes. This is done to help the refrigerant pressures stabilize and reduce hard starting of the compressor.
This unit can be put into a diagnostic mode.
1.Unplug unit
2.Install jumper on pins 9 and 10 on board.
3.Plug unit back in.
Based on the attached chart you can turn on and off each relay individually.
POT
2 3 4 5
TOP DRAWER
THERMISTOR 9 & 10 PINS
1 2 3 4 5 6 7 8 9 10
BOTTOM DRAWER
THERMISTOR
TOP | COND/GAS | COMPRESSOR | 1 | |
0 | ||||
VALVE | FAN | |||
| ||||
|
|
|
BOTTOM
VALVE
POWER | TOP |
| |
| LIGHT |
BOTTOM
LIGHT
Control pot at 2 – bottom light Control pot at 0 – top light
Control pot at
POWER ON
DISPLAY BOARD
CONNECTION
CONDENSER
FAN
J2TOP VALVE
1/4" SPADE
TERMINALS
CLRCO035C
Jumper on 1/4" spade terminals – COMPRESSOR Jump pins on J2 – TOP VALVE
Jump pins on J2 – CONDENSER FAN
26