VENT TERMINATION CLEARANCES:

INSTALLATION

VENT TERMINATION CLEARANCES:

A)Minimum 4-foot clearance below or beside any door or window that opens.

B)Minimum 1-foot clearance above any door or window that opens.

C)Minimum 3-foot clearance form any adjacent building.

D)Minimum 7-foot clearance from any grade when adjacent to public walkways.

E)Minimum 2-foot clearance above any grass, plants, or other combustible materials.

F)Minimum 3-foot clearance from an forced air intake of any appliance.

G)Minimum 2-foot clearance below eves or overhang.

H)Minimum 1-foot clearance horizontally from combustible wall.

I)Must be a minimum of 36-inches above the roof and 24-inches above the highest point or the roof within 10- feet.

I

B

A

F

CH

A

F

D

E Manual background

FIGURE 6

VENT TERMINATION CLEARANCES

-9-