SPECIAL MOBILE HOME REQUIREMENTS

INSTALLATION

SPECIAL MOBILE HOME REQUIREMENTS

WARNING! - DO NOT INSTALL IN A SLEEPING ROOM

CAUTION! - THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL, AND CEILING/ ROOF MUST BE MAINTAINED.

In addition to the previously detailed installation requirements, mobile home installations must meet the following requirements:

The stove must be permanently attached to the floor.

The stove must have a permanent outside air source (USSC Part No FAK1780 Fresh Air Kit is recommended).

The stove must be electrically grounded to the steel chassis of the mobile home with 8 GA copper wire using a serrated or star washer to penetrate paint or protective coating to ensure grounding.

Vent must be 3 or 4-inch “PL” Vent and must extend a minimum or 36-inches above the roofline of the mobile home and must be installed using a UL/ULC listed ceiling fire stop and rain cap.

When moving your mobile home, all exterior venting must be removed while the mobile home is being relo- cated. After relocation, all venting must be reinstalled and securely fastened.

Check with your local building officials as other codes may apply.