Vanguard Heating VMH10TNB Vent-Freenatural Gas Compact Fireplace, Installation, Continued

Models: VMH10TNB

1 28
Download 28 pages 40.09 Kb
Page 16
Image 16
Pressure Testing Gas Supply Piping System

Pressure Testing Fireplace Gas ConnectionsManual backgroundManual backgroundManual background®VMH10TNB

VENT-FREE NATURAL GAS COMPACT FIREPLACE

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

Manual background WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

Manual backgroundWARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.

Disconnect appliance with its appliance

 

main gas valve (control valve) and equip-

 

ment shutoff valve from gas supply pip-

 

ing system. Pressures in excess of 1/2

 

psig will damage heater regulator.

2.

Cap off open end of gas pipe where

 

equipment shutoff valve was connected.

3.

Pressurize supply piping system by ei-

 

ther using compressed air or opening

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Fig- ure 26).

2.Pressurize supply piping system by ei- ther using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to equipment shutoff valve (see Figure 27). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Equipment

Shutoff

ValveOpen

Closed

Figure 26 - Equipment Shutoff Valve

Pressure Testing Fireplace Gas Connections

1.Open equipment shutoff valve (see Fig- ure 26).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of fireplace is in the OFF position.

4.Check all joints from equipment shutoff valve to thermostat gas valve (see Fig- ure 27). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Light fireplace (see Operating Fire- place, pages 17 and 18). Check all other internal joints for leaks.

7.Turn off fireplace (see To Turn Off Gas to Appliance, page 18).

8.Replace front panel.

 

main gas valve located on or near gas

 

meter.

4.

Check all joints of gas supply piping

 

system. Apply mixture of liquid soap

 

and water to gas joints. Bubbles form-

 

ing show a leak.

5.

Correct all leaks at once.

6.

Reconnect fireplace and equipment

 

shutoff valve to gas supply. Check re-

 

connected fittings for leaks.

Gas Meter

Equipment

Shutoff

Valve

Figure 27 - Checking Gas Joints

16

107031