Vermont Castings Madison
• Placing a chimney connector pipe inside a section |
of 9" (230 mm) diameter, |
built chimney, with two inches of air space between |
the chimney section and combustibles. (Fig. 10) |
Min. 18"
(460mm) Chimney clearance to sheet steel 2" (51mm)
supports and combustibles Min.
Canadian Requirements:
In Canada, the Canadian Standards Association has established specific guidelines regarding wall pass- though design. Figure 11 shows one approved method in which all combustible material in the wall is cut away to provide the required 18" (460 mm) clearance around the connector. The resulting space must remain empty. A
24 ga. Sheet Steel Support (one side only)
ST276
Flue | Min. 18" |
(460mm) | |
Chimney | Chimney |
| |
| Connector |
| 24 ga.Sheet |
| Steel Support |
| Masonry Chimney |
| constructed to CAN/CSA- |
| B365 |
used on one side only. If covers must be used on both sides, each cover must be mounted on noncombus- tible spacers at least 1" (25 mm) clear of the wall. Your local dealer or your local building inspector can provide details of other approved methods of passing a chimney connector through a combustible wall.
In Canada, this type of installation must conform to
Chimney clearance to sheet |
| |
steel supports and combustibles | 2" (51mm) Min. | |
Steel Thimble |
|
|
with two 1" |
|
|
(25mm) Ventilated |
| Min. 6" |
Channels |
| (152mm) |
|
| |
| Flue | Chimney Connector |
| Chimney | Glass Fiber |
Masonry Chimney |
| Insulation |
constructed to NFPA 211 |
|
|
|
| 24 ga.Sheet |
|
| Steel Supports |
ST274
Fig. 9 Wall
Fig. 11 CSA approved Wall
Floor Protection
A tremendous amount of heat radiates from the |
bottom plate of your Madison. The floor area directly |
under and around the stove will require protection from |
radiant heat as well as from stray sparks or embers |
that may escape the firebox. |
Heat protection is provided through the use of a |
Vermont Castings Bottom Heat Shield #1892. Spark |
and ember protection must be provided by a floor |
protector constructed with noncombustible material as |
specified. |
Most installations will require that the bottom heat |
shield be attached. Only when the stove is placed on a |
completely noncombustible surface such as unpainted |
concrete over earth may it be used without the heat shield. |
Even when the bottom heat shield is installed, you |
must provide special protection to the floor beneath. |
For installations with the heat shield attached, use a |
noncombustible floor protector such as 1/4” non- |
asbestos mineral board or equivalent, or 24 gauge |
sheet metal. The floor protector may be covered with a |
noncombustible decorative material if desired. Do not |
obstruct the space under the heater. |
Protection requirements vary somewhat between |
the United States and Canada as follows: |
For U.S. installations the floor protector is re- |
Chimney clearance to sheet steel supports and combustibles
2" (51mm) Min.
air spaceFlue Chimney
Prefab Chimney Section
24 ga. Sheet Steel Supports
ST275
2" (51mm)
Min.
2" (51mm) Min.
Chimney
Connector
Prefab
Chimney
Section
24 ga. Sheet Steel Supports
Masonry Chimney constructed to NFPA 211
quired under the stove and must extend at least 18” |
from the front of the stove (“D”, Fig. 12), at least 4” |
from the right side and rear (“C”, Fig. 12) and 16” from |
the left side (“E”, Fig. 12). It must also extend under |
the chimney connector and 2” to either side (“F”, Fig. |
12). |
To meet these requirements, a floor protector must |
be at least 48” wide (“A”,Fig. 12) and 48” deep (“B”,Fig. |
12) |
In Canada, a noncombustible floor protector is |
required under the heater also. The floor protector |
Fig. 10 Wall
must extend 18” (460 mm) to the front (D), and 8” (203 |
mm) from the right side (C) and rear (C) and 18” |
(460mm) from left side (E). |
8