Vermont Casting 1655, 1656, 1657, 1658, 1659 Wall Shields, Vermont Castings Madison, Max. - C

Models: 1655, 1656, 1657, 1658, 1659

1 28
Download 28 pages 24.08 Kb
Page 10
Image 10
Wall Shields

Vermont Castings Madison

Wall Shields

Wall shields should be constructed of 24 gauge or heavier sheet metal, or another noncombustible material such as 1/2" (13 mm) insulation board (Fig.

14)or common brick "laid on flat," with the 3¹⁄₂" (90 mm) side down.

Shields must be spaced out from the combustible surface 1" (25 mm) on noncombustible spacers. The spacers should not be directly behind the stove or chimney connector.

Air must be able to flow between the wall and the shield. At least 50% of the bottom 1" (25 mm) of the shield should be open and the shield must be open at the top.

Air flow

 

Stud wall

 

framing

 

Wall shield

 

Noncombustible

 

spacers and

Shield

fasteners

 

Drywall

Metal Spacer

 

Air flow

ST248a

Fig. 14 Approved Wall shield construction

The following examples of wall shield construction illustrate common designs used to safely achieve reduced clearances to combustible wall materials.

Parallel installation, vertical chimney connector, two wall shields. Fig. 15: Reduced clearances for both rear and side walls. Wall shields may meet at corner if desired. Shielding for connector is centered behind connector.

Parallel installation with rear wall pass-through, two wall shields. Fig. 16: Reduced clearances for both rear and side walls. Wall shields may meet at corner if desired. Shielding for connector is centered behind connector. Wall pass-through must comply with codes.

Corner installation, vertical chimney connector, two wall shields. Fig. 17: Reduced side clearances. Wall shields MUST meet at corner.

Parallel installation with rear exit, rear wall pass- through, rear wall shield. Fig. 18: Reduced clearances for rear wall. Shielding for connector is centered behind connector. Wall pass-through must comply with codes.

 

 

C

 

C

 

A =

48” (1219 mm)

 

 

 

 

 

 

 

 

 

A

 

B

B =

Max. - C

 

B

A

 

C =

1” (25 mm)

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ST550

Fig. 15

Parallel installation, vertical chimney connector, two

wall shields.

 

 

A =

48” (1219 mm)

 

 

B =

48” (1219 mm)

 

 

C =

1” (25 mm)

 

A

A

 

 

B

B

 

 

C

C

 

 

 

 

 

 

 

ST551

Fig. 16

Parallel installation with rear wall pass-through, two

wall shields.

 

 

C

C

 

A =

48” (1219 mm)

 

 

 

 

 

 

 

 

A

B

B =

Max. - C

 

B

 

 

C = 1” (25 mm)

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

C

 

 

C

 

 

 

 

 

 

 

 

ST552

Fig. 17

Corner installation, vertical chimney connector, two

wall shields.

A =

48” (1219 mm)

B =

48” (1219 mm)

C = 1” (25 mm)

A

 

B

 

C

 

 

ST564

 

Fig. 18 Parallel installation, rear wall pass through, rear wall

10

shield.

 

Page 10