Vermont Casting 1920 installation instructions Aspen Clearance Chart, Aspen Woodburning Stove

Models: 1920

1 32
Download 32 pages 919 b
Page 13
Image 13
Aspen Clearance Chart

Aspen Woodburning Stove

Aspen Clearance Chart

Use the chart below together with the diagrams on the next page to determine the required clearance for your particu- lar installation.

Stove clearances are measured from the top plate to the combustible surface.

Chimney connector clearances are measured from the connector surface and take into account flue collar offset.

 

 

Unprotected Surfaces

 

Protected Surfaces

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Corner

 

 

 

 

Corner

 

 

Parallel Installation

 

Installation

 

Parallel Installation

 

Installation

Stove Clearance

 

Side

Rear

 

Corner

 

Side

Rear

 

Corner

No Heat Shields

(A) 24”

(B) 13”

 

(C) 13”

 

(D) 16”

(E) 9”

 

(F) 8”

 

 

(610 mm)

(330 mm)

 

(330 mm)

 

(406 mm)

(230 mm)

 

(203 mm)

Top Exit, Rear Heat

(G) 24”

(H) 11”

 

(I) 13”

 

(J) 16”

(K) 9”

 

(L) 8”

Shield ONLY1

(610 mm)

(179 mm)

 

(330 mm)

 

(406 mm)

(230 mm)

 

(203 mm)

Rear Exit, Rear Heat

(M) 24”

(N) 11”

 

N/A

 

(O) 16”

(P) 9”

 

N/A

Shield ONLY

(610 mm)

(179 mm)

 

 

 

(406 mm)

(230 mm)

 

 

Top Exit, Rear H.S., Single-

(Q) 24”

(R) 9”

 

(S) 13”

 

(T) 16”

(U) 9”

 

(V) 8”

wall, connector shields1,2

(610 mm)

(229 mm)

 

(330 mm)

 

(406 mm)

(230 mm)

 

(203 mm)

Top Exit, Rear H.S., Double-

(Q) 24”

(R) 7”

 

(S) 13”

 

(T) 16”

(U) 7”

 

(V) 8”

wall connector shields 1,3

(610 mm)

(178 mm)

 

(330 mm)

 

(406 mm)

(178 mm)

 

(203 mm)

Chimney Connector

Unprotected Surface / Vertical

 

Protected Surface / Vertical

No Heat Shields

 

15” (381 mm)

 

 

 

11” ( 279 mm)

 

Using Connector Heat Shields2

 

13” (330 mm)

 

 

 

6” (152 mm)

 

Double Wall Connector3

 

6” (152 mm)

 

 

 

6” (152 mm)

 

 

 

Unprotected Surface / Horizontal

 

Protected Surface / Horizontal

Single Wall Connector

 

18” (457 mm)

 

 

 

11” (279 mm)

 

Double Wall Connector

 

6” (152 mm)

 

 

 

6” (152 mm)

 

Front Clearance

 

 

 

All Installations

 

 

 

to Combustibles

 

 

 

48” (1219 mm)

 

 

 

** A distance of 48” must be maintained between the stove and moveable combustible items such as drying clothes, furni- ture, firewood, etc.

1 When a rear heat shield is installed on a top exit stove, the shield insert must be attached to the shield so the area behind the flue collar on the stove is protected.

2 Chimney connector heat shields must extend exactly 24” (610 mm) above the top of the stove. No shielding can be used on the connector above 24” (610 mm). The unshielded chimney connector above the 24” (610 mm) point must be 13” (330 mm) from an unprotected wall.

3 In top exit installations, this clearance requires the use of the rear stove heat shield with the flue collar cover plate installed.

30000369

13

Page 13
Image 13
Vermont Casting 1920 installation instructions Aspen Clearance Chart, Aspen Woodburning Stove