Masonry Chimneys, cont’d.
•Unused openings in an existing masonry chimney must be sealed with masonry to the thickness of the chimney wall, and the chimney liner should be repaired. Openings sealed with pie plates or wallpa- per are a hazard and should be sealed with mortar or refractory cement. In the event of a chimney fire, flames and smoke may be forced out of these unused thimbles.
•The chimney should be thoroughly cleaned before use.
•A
Prefabricated Chimneys
A prefabricated metal chimney must be one that is test- ed and listed for use with
Chimney Size
This stove is approved for venting into a masonry chim- ney with a nominal flue size of 8” x 8” (203 x 203 mm), and into a round flue size of 8” (203 mm) or 6” (152 mm).
It may be vented into larger chimneys as well. However, chimneys with liners larger than 8” x 12” (203 x 305 mm) may experience rapid cooling of smoke and reduction in draft, especially if they are located outside the home. Such large chimneys may need to be insulated or have the flue relined for proper stove performance.
Do not connect this unit to a chimney flue serv- ing another appliance.
NOTE: Do not vent this stove into a
Do not connect the STOVE to any air distribu- tion duct or system.
Aspen Woodburning Stove
Ask your dealer about components available for con- necting the stove to a steel chimney liner.
Chimney Connector Guidelines
A chimney connector is the
If possible, do not pass the chimney connector through a combus- tible wall or ceiling. If
passage through a combustible wall is
unavoidable, refer to the recommendations in the section follow- ing on Wall Pass- throughs. Do not pass the connector through an attic, a closet or any similar concealed
space. The whole chimney connector should be ex- posed and accessible for inspection and cleaning.
Install the single wall chimney connector not less than 18” (457mm) from the ceiling. Keep it as short and direct as possible, with no more than two 90 degree turns. If possible, use 45° elbows. Slope horizontal runs of connectors upward 1/4” per foot (20mm per meter) going from the stove toward the chimney. The recommended maximum length of a horizontal run is 3’ (914mm), and the total length of chimney connector should be no longer than 8’ (2.5 meters).
In cathedral ceiling installations, extend the prefabri- cated chimney downward to within 8 feet (2.4m) of the stove.
SAFETY NOTE: Always wear gloves and protective eyewear when drilling, cutting or joining chimney connector sections .
30000369 | 5 |