![Accessories are available for use as wall pass- throughs. If using one of these, make sure it has been tested and listed for use as a wall pass-through.](/images/new-backgrounds/53132/5313215x1.webp)
Resolute Acclaim Woodburning Stove
Accessories are available for use as wall pass- throughs. If using one of these, make sure it has been tested and listed for use as a wall pass-through.
U.S.: In the United States, the National Fire Protec- tion Association (NFPA) has established guidelines for passing chimney connectors through combus- tible walls. Many building code inspectors follow these guidelines when approving installations.
The following illustration shows one
Three other methods are also approved by the NFPA. These are:
•Using a section of
•Placing a chimney connector pipe inside a ven- tilated thimble, which is then separated from combus- tibles by 6” (152 mm) of fiberglass insulating material.
•Placing a chimney connector pipe inside a sec- tion of 9” (229 mm) diameter,
Canada: The Canadian Standards Association has established different guidelines. The illustration below shows one method, in which all combus- tible material in the wall is cut away to provide the required 18” (457 mm) clearance for the connector. The resulting space must remain empty. A flush- mounted sheet metal cover may be used on one side only. If covers must be used on both sides, each cover must be mounted on noncombustible spacers at least 1” (25 mm) clear of the wall. Your local dealer or your local building inspector can provide details of other approved methods of pass- ing a chimney connector through a combustible wall.
In Canada, this type of installation must conform to
NOTE: Do not vent your Resolute Acclaim into a
DO NOT CONNECT THE RESOLUTE ACCLAIM TO ANY AIR DISTRIBUTION DUCT OR SYSTEM.
Wall Stud
Chimney Con- nector
T
Floor Pro- tection
12” (305mm) of Noncombustible Material
ST493a
18” (457 mm) clear- ance all around the pipe
TT
Flush
Mounted
ST494a
Fig. 9 An approved wall
Fig. 10 An approved wall
8 | 2000893 |