Vermont Casting 2490 installation instructions Resolute Acclaim Woodburning Stove, 2000893

Models: 2490

1 32
Download 32 pages 15.33 Kb
Page 8
Image 8
Accessories are available for use as wall pass- throughs. If using one of these, make sure it has been tested and listed for use as a wall pass-through.

Resolute Acclaim Woodburning Stove

Accessories are available for use as wall pass- throughs. If using one of these, make sure it has been tested and listed for use as a wall pass-through.

U.S.: In the United States, the National Fire Protec- tion Association (NFPA) has established guidelines for passing chimney connectors through combus- tible walls. Many building code inspectors follow these guidelines when approving installations.

The following illustration shows one NFPA-recommend- ed method. All combustible material in the wall is cut away a sufficient distance from the single-wall connec- tor to provide the required 12” (305 mm) clearance for the connector. Any material used to close up the open- ing must be noncombustible.

Three other methods are also approved by the NFPA. These are:

Using a section of double-wall chimney with a 9” (229 mm) clearance to combustibles.

Placing a chimney connector pipe inside a ven- tilated thimble, which is then separated from combus- tibles by 6” (152 mm) of fiberglass insulating material.

Placing a chimney connector pipe inside a sec- tion of 9” (229 mm) diameter, solid-insulated, factory- built chimney, with 2” (51 mm) of air space between the chimney section and combustibles.

Canada: The Canadian Standards Association has established different guidelines. The illustration below shows one method, in which all combus- tible material in the wall is cut away to provide the required 18” (457 mm) clearance for the connector. The resulting space must remain empty. A flush- mounted sheet metal cover may be used on one side only. If covers must be used on both sides, each cover must be mounted on noncombustible spacers at least 1” (25 mm) clear of the wall. Your local dealer or your local building inspector can provide details of other approved methods of pass- ing a chimney connector through a combustible wall.

In Canada, this type of installation must conform to CAN/CSA-B365, Installation Code for Solid Fuel Burn- ing Appliances and Equipment.

NOTE: Do not vent your Resolute Acclaim into a factory-built (zero-clearance) fireplace under any circumstances. The Resolute Acclaim has not been specifically tested and listed for this type of in- stallation. These appliances and their chimneys are specifically designed as a unit for use as fireplaces. It may void the listing or be hazardous to adapt them for any other use.

DO NOT CONNECT THE RESOLUTE ACCLAIM TO ANY AIR DISTRIBUTION DUCT OR SYSTEM.

Wall Stud

Chimney Con- Manual background nector Manual backgroundManual background

T

Floor Pro- tection

12” (305mm) of Noncombustible Material

ST493a

18” (457 mm) clear- ance all around the pipe

TTManual backgroundManual backgroundManual background

Flush

Mounted

ST494a

Fig. 9 An approved wall pass-through for the United States.

Fig. 10 An approved wall pass-through for Canada.

8

2000893

Page 8
Image 8
Vermont Casting 2490 installation instructions Resolute Acclaim Woodburning Stove, 2000893