360 DVS Series Direct Vent Fireplaces
Clearance to Combustibles
Appliance |
|
Top | 0” (0 mm) to standoff |
Bottom | 0” (0 mm) |
Vent End | 1/2” (13 mm) to rear panel |
Nonvent End (DVS2) | 0” (0 mm) |
Venting |
|
Concentric sections of DV Vent: |
|
Top, bottom & sides | 1” (25 mm) |
Nonconcentric sections of DV Vent: |
|
Side and bottom | 1” (25 mm) |
Top | 2” (51 mm) |
Mantels
The height at which a combustible mantel is fitted above the fireplace is dependent on the depth of the mantel. This also applies to the distance between the mantel leg (if so fitted) and the fireplace. For correct mounting height and width, refer to Fig. 4a and 4b and the Mantel Chart below.
The fitting of a bay window trim kit does not affect the distances and reference points referred to in the dia- gram and chart.
Noncombustible mantels and legs may be installed at any height and width around the appliance.
When using paint or lacquer to finish the mantel, such paint or lacquer must be heat resistant to prevent dis- coloration.
| Top View |
|
|
|
|
|
|
| J | I H | G |
| Mantel Leg |
|
|
| |
|
|
|
| F | |
CFM197 |
|
|
|
|
|
Front View |
|
| K |
| |
|
| ML |
| ||
|
|
|
|
| |
| Side of Combustion |
|
| N |
|
| Chamber |
|
| O |
|
|
|
|
|
| |
|
|
|
|
| Mantel |
|
|
|
|
| Leg |
|
|
|
|
| CFM170 |
| Mantel |
| Mantel Leg From Side | ||
Ref. | Leg Depth | Ref. | of Comb. Opening | ||
F | 10” (254 mm) | K | 11¹⁄₂” (292 mm) |
V
W
X
Y
Z
A B C D E
Bottom of Door Trim
Fireplace |
Louvre Assembly |
Top |
Top of Combustion |
Chamber |
CFM146 |
G | 8” (203 mm) | L | 9¹⁄₂” (241 mm) |
H | 6” (152 mm) | M | 7¹⁄₂” (191 mm) |
I | 4” (102 mm) | N | 5¹⁄₂” (140 mm) |
J | 2” (51 mm) | O | 3¹⁄₂” (89 mm) |
|
| ||
Fig. 4b | Combustible mantel leg minimum installation. |
Hearth
A hearth is not mandatory; however, for aesthetic purposes, we recommend installing a noncombustible hearth that projects out 12” (305mm) or more from the front of the fireplace.
Cold climate installation recommendation:
When installing this unit against a noninsu-
| Mantel Chart | ||
| Mantel Shelf |
| Mantel from Top |
Ref. | or Breast Plate | Ref. | of Comb. Chamber |
V | 10” (254 mm) | A | 19” (483 mm) |
W | 8” (203 mm) | B | 17” (432 mm) |
X | 6” (152 mm) | C | 15” (381 mm) |
Y | 4” (102 mm) | D | 13” (330 mm) |
Z | 2” (51 mm) | E | 11” (297 mm) |
|
|
|
|
Fig. 4a | Combustible mantel minimum installation. |
lated exterior wall or chase, it is mandatory the outer walls be insulated to conform to applicable insulation codes.
8 | 10006326 |