Vermont Casting 43LDVT manual General Venting, LDVT Series Direct Vent GaS Fireplace, 10007852

Models: 3LDVT 36LDVT 39LDVT 43LDVT

1 40
Download 40 pages 2.33 Kb
Page 9
Image 9
General Venting

LDVT Series Direct Vent GaS Fireplace

 

BLACK

 

 

 

 

L1

 

 

 

 

WHITE

 

 

 

 

L2

 

 

POWER CORD

 

 

 

 

 

 

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PURPLE

PILOT SENSING PILOT IGNITER

CIRCUIT BOARD

YELLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

 

 

 

 

 

 

 

 

BLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ORANGE

 

 

 

 

 

 

 

 

RED

 

ON/OFF SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHITE

 

OR

 

 

 

 

 

 

WALL THERMOSTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP1571

Fig. 9 SIT822 Valve with Synetek electronic control wiring diagram.

General Venting

Your fireplace is approved to be vented either through the side wall, or vertically through the roof.

Only CFM Corporation venting components spe- cifically approved and labelled for this fireplace may be used.

Vent terminations shall not be recessed into a wall or siding.

Horizontal venting which incorporates the twist lock pipe must be installed on a level plane without an inclining or declining slope.

Horizontal venting which incorporates the use of flex venting shall have an inclining slope from the unit of 1” (25 mm) per 24” (610 mm).

There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within 24” (610 mm) from the front of the termination hood.

Do not locate termination hood where excessive snow or ice build up may occur. Be sure to check vent termi- nation area after snow falls, and clear to prevent ac- cidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.

Location of Vent Termination

It is imperative the vent termination be located observ- ing the minimum clearances as shown on the next page.

*Check with local codes or in absence of same with CSA-B149.1 Installation Codes (1991) for Canada or follow the current National Fuel Gas Code, ANSI Z223.1/NFPA 54 for installations in the USA.

10007852