DV Power Vent System
Troubleshooting the Power Vent System
SIT 822 Valve with Synetek Electronic Ignitor and Synetek Power Vent Board
Service must be performed by a qualified installer, service agency or your gas supplier.
BEFORE COMMENCING TO TROUBLE SHOOT THE UNIT:
1.Check if there is power to the unit (fireplace) and to the power vent box.
2.Check if there is gas to the unit (fireplace).
3.The ignition control in the fireplace is equipped with a lockout device which will put the unit into a lockout condition after three attempts to ignite the pilot. Follow the steps in the chart below to reset the control: Turn the On/Off switch to the off position, or turn the thermostat to the off position.
Wait 10 seconds and then turn to the “on” position.
4.If this is the first time that the unit has been fired, check the wiring of the unit against the wiring diagram before commencing troubleshooting.
START |
|
|
|
|
|
|
|
|
|
| ||||
ON/OFF switch or wall thermostat “ON”? |
|
|
|
|
|
|
|
| ||||||
|
|
|
| NO | Is there 120V power to the fireplace and power vent? |
|
|
|
|
|
|
| ||
Power vent motor | Are all wiring connections tight? (Turn off Power before checking) |
|
|
|
|
|
| |||||||
is working? |
| Is the LED light on the ignition control board giving an error code? (Refer to Page 14) |
|
|
| |||||||||
| YES |
| YES | YES | Is there 120V Power to the motor? | YES |
| |||||||
| Is there 24V at the power vent circuit |
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
| board at the 24VAC Hot Terminal? |
|
|
|
| NO |
|
| ||
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
| NO |
| Replace Power Vent Circuit Board |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Check R & W from ignition control board are not crossed between power |
|
|
|
|
|
| ||||||
|
| vent circuit board and ignition control board. (R) 24V AC Hot must con- |
| Replace ignition control board |
| |||||||||
|
|
|
| |||||||||||
|
| nect to 24V AC Hot at power vent circuit board. (W) Thermostat must |
|
|
|
|
|
| ||||||
|
| connect to ignition control Hot at power vent circuit board. |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Replace Blower
Does the Pilot
Spark?
YES
NO
Is there 24V power at terminal 7 (24V) at the ignition board?
YES
Is the lead to the spark electrode attached or arcing to ground?
Is the electrode cracked?
NO
NO
Is the Pressure Switch Closed?
YES
Replace Power
Vent Circuit Board
NO
Is there a blockage in the vent? Is there water/dirt in the hose from blower to the pressure switch? Are hose connections loose?
Is the hose cracked?
Is the hose connected to the low pressure side of the pressure switch?
NO
Replace
Pressure
Switch
|
|
|
| Replace Ignition Module |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| NO |
|
|
|
|
|
|
| YES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
Pilot Burner | Is there 24V power at terminal |
| Is pilot gas line blocked? |
| NO |
|
|
|
|
|
|
|
|
|
| |||||||||||||||||
Lights? |
| 3 (PV) during spark cycle? |
|
|
| Is pilot orifice blocked? |
| Replace Gas Valve |
|
|
|
|
| |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Are wires to valve loose |
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
| NO |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
| YES |
|
|
|
|
|
|
|
|
|
|
| or corroded? |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
NO | Replace Ignition Module | YES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
Does Spark | Does pilot flame cover |
|
|
| Is flame rod corroded? |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
Stop When |
| the flame rod? |
|
|
|
|
|
|
| Is pilot hood corroded? |
|
| NO |
| Replace Ignition Module |
| ||||||||||||||||
Pilot Lights? |
|
|
|
|
|
|
|
|
|
| Is flame rod insulator cracked? |
|
|
| ||||||||||||||||||
|
| NO |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| Is wire to flame rod damaged? |
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
| YES |
| Check Pilot for obstruction |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
| Check Gas Pressure |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| Adjust Pilot Flame |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Check | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| Is there 24V power at terminal |
| YES |
|
|
|
|
|
| NO | Is there manifold pressure? | YES |
| position | |||||||||||||||
Does Main | NO |
|
| Are wires to valve |
|
| ||||||||||||||||||||||||||
2 main valve hot during spark |
|
|
|
| ||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| of pilot. | |||||||||||||||
Burner Light? |
| cycle? |
|
|
|
|
|
| loose or corroded? |
|
|
|
|
|
|
| NO |
|
|
| Is orifice | |||||||||||
|
|
|
|
| NO |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Replace Gas Valve |
|
|
|
| blocked? | |||||||
|
| YES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
| Replace Ignition Module |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Is vent partially blocked? |
|
|
|
|
|
| ||||||
System Runs |
| Is the correct size of orifice restrictor installed in the power vent? |
| Is there water/dirt in hose to |
|
|
|
|
|
| ||||||||||||||||||||||
Continuously | NO | Does the pilot flame covers the flame rod? |
|
|
|
|
|
|
| pressure switch? |
|
|
|
|
|
| ||||||||||||||||
Until Switched |
| Is the flame rod wire in good condition? |
|
|
|
|
|
|
| Are hose connections loose? |
| NO |
| Replace | ||||||||||||||||||
| Off? |
| Is there continuity to ground from the pilot burner? |
|
|
| Is the hose cracked? |
|
| Pressure | ||||||||||||||||||||||
|
|
|
|
|
|
|
|
| ||||||||||||||||||||||||
|
|
|
|
|
|
|
| |||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Is the hose connected to the |
|
|
|
|
|
| ||||||
|
|
|
|
| YES |
|
|
|
|
|
|
|
|
|
|
|
|
| low pressure side of the pres- |
|
|
|
|
| Switch | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
| Does pressure switch open during operation? | YES |
|
|
| sure switch? |
|
|
|
|
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| NO |
|
|
|
|
|
|
|
|
|
| YES |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Replace power vent circuit board |
|
|
| |||||||||||
| Does 24V power get interupted at terminal 7 (24V) at the ignition module? |
|
|
|
|
|
|
|
| |||||||||||||||||||||||
|
|
|
|
|
|
|
|
| ||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| NO |
|
|
|
|
|
|
| WARNING: Never jump the pressure switch out of this | |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||
|
|
|
| Replace ignition module |
|
|
|
|
|
|
| |||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
| system. Property damage, injury or death may result. | |||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|