Vermont Casting DVT38 Troubleshooting the Gas Control System, Chateau, Symptom, Possible Causes

Models: DVT38

1 40
Download 40 pages 28.48 Kb
Page 27
Image 27
Troubleshooting the Gas Control System

Chateau™

Troubleshooting the Gas Control System

SIT NOVA 820 MILLIVOLT VALVE

NOTE: Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position.

 

Symptom

Possible Causes

Corrective Action

 

 

 

 

1.

Spark ignitor will not light

A. Defective or misaligned electrode

Using a match, light pilot. If pilot lights, turn off pilot and

 

 

at pilot

push the red button again. If pilot will not light - check

 

 

 

gap at electrode and pilot-should be 1/8” to have a

 

 

 

strong spark.

 

 

B. Defective ignitor (Push Button)

With the control knob in the pilot position, push the

 

 

control knob all the way and hold. Check for spark at

 

 

 

electrode and pilot. If no spark to pilot, and electrode

 

 

 

wire is properly connected, replace the battery in the

 

 

 

ignitor module and try again. Refer toMaintenance

 

 

 

Section. If the problem still exists, replace the ignitor

 

 

 

module box.

2. Pilot will not stay lit after

A. Defective pilot generator (thermo-

Check pilot flame. Must impinge on thermocouple/ther-

 

carefully following lighting

couple), remote wall switch

mopile. NOTE: This pilot burner assembly utilizes both

 

instructions

 

a thermocouple and a thermopile. The thermocouple

 

 

 

operates the main valve operation (On and Off). Clean

 

 

 

and or adjust pilot for maximum flame impingement on

 

 

 

thermopile and thermocouple.

 

 

B. Defective automatic valve

Turn valve knob to “Pilot”. Maintain flow to pilot; millivolt

 

 

 

meter should read greater than 10mV. If the reading

 

 

 

is okay and the pilot does not stay on, replace the gas

 

 

 

valve. NOTE: An interrupter block (not supplied) must

 

 

 

be used to conduct this test.

3.

Pilot burning, no gas to

A. Wall switch or wires defective

Check wall switch and wires for proper connections.

Jumper wire across terminals at wall switch, if burner

 

main burner

 

 

 

comes on, replace defective wall switch.. If okay,

 

 

 

 

 

 

jumper wires across wall switch wires at valve, if burner

 

 

 

comes on, wires are faulty or connections are bad.

 

 

B. Thermopile may not be generat-

1. Be sure wire connections form thermopile at gas

 

 

ing sufficient millivoltage

valve terminals are tight and thermopile is fully

 

 

 

inserted into pilot bracket.

 

 

 

2. One of the wall switch wires may be grounded. Re-

 

 

 

move wall switch wires form valve terminals if pilot

 

 

 

now stays lit, trace wall switch wiring for ground.

 

 

 

May be grounded to fireplace or gas supply.

 

 

 

3. Check thermopile with millivolt meter. Take reading

 

 

 

at thermopile terminals of gas valve. Should read

 

 

 

250-300 millivolts (minimum 150) while holding

 

 

 

valve knob depressed in pilot position and wall

 

 

 

switch “Off”. Replace faulty thermopile if reading is

 

 

 

below specified minimum.

 

 

C. Plugged burner orifice

Check burner orifices for debris and remove.

 

 

D. Defective automatic valve opera-

Turn valve knob to “On”, place wall switch to “On”

 

 

millivolt meter should read greater than 150mV. If the

 

 

tor

 

 

reading is okay and the burner does not come on,

 

 

 

replace the gas valve.

4.

Frequent pilot outage

A. Pilot flame may be too low or

Clean and/or adjust pilot flame for maximum flame

 

problem

blowing (high) causing the pilot

impingement on thermopile and thermocouple.

 

 

safety to drop out

 

 

 

B. Possible blockage of the vent

Check the vent terminal for blockage (recycling the flue

 

 

terminal

gases).

20006081

27

Page 27
Image 27
Vermont Casting DVT38 Troubleshooting the Gas Control System, Chateau, SIT NOVA 820 MILLIVOLT VALVE, Symptom