Vulcan-Hart VGF-18 operation manual Testing The Gas Supply System, Flue Connections

Models: VGF-18

1 12
Download 12 pages 3.39 Kb
Page 7
Image 7
TESTING THE GAS SUPPLY SYSTEM

TESTING THE GAS SUPPLY SYSTEM

When test pressures exceed 1/2 psig (3.45 kPa), the fryer and its individual shutoff valve must be disconnected from the gas supply piping system.

When test pressures are 1/2 psig (3.45 kPa) or less, the fryer must be isolated from the gas supply system by closing its individual manual shutoff valve.

FLUE CONNECTIONS

DO NOT obstruct the flow of flue gases from the flue located at the rear of the fryer. It is recommended that the flue gases be ventilated to the outside of the building through a ventilation system installed by qualified personnel.

Adequate ventilation must be provided and must comply with NFPA Standard #96 (latest edition), and with local codes.

Never make flue connections directly to the fryer.

The fryer must be located under a hood which has an adequate connection to an exhaust duct. The hood must extend 6" (152.4 mm) beyond fryer sides.

Clearance above fryer should be adequate for products of combustion to be removed efficiently. An 18" (457 mm) minimum clearance should be maintained between the flue vent and the filters of the hood venting system.

Information on the construction and installation of ventilating hoods may be obtained from the standard for "Vapor Removal from Cooking Equipment," NFPA No. 96 (latest edition), available from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269.

Adequate air should be provided in the kitchen to replace air taken out by the ventilating system. This will prevent fryer function from being affected by a reduced atmospheric pressure.

— 7 —

Page 7
Image 7
Vulcan-Hart VGF-18 operation manual Testing The Gas Supply System, Flue Connections