Operating Instructions & Parts Manual

JSU50

Maintenance (Continued)

pre-charged TANKS

If a pre-charged tank becomes water- logged, the bladder is probably leaking or broken.

1.Test the tank by depressing the air valve. The valve will discharge water if the bladder is broken.

2.If bladder is broken, replace tank.

Once a tank bladder is ruptured, the tank should be replaced. Repairing the bladder is not recommended, and may cause further problems such as: repeated water-logging, debris in pipes and clogged discharge in tank.

air pressure check for pre- charged tanks

Small amounts of air loss is normal in any tank. To prevent failure and properly maintain a pre-charged water tank, check the pressure on a yearly basis.

1.Disconnect power to pump.

2.Open a faucet nearest the tank and allow all water to drain from the tank.

3.Measure the tank pre-charge at the valve stem using a tire gauge.

4.If necessary, adjust the pre-charge with an air pump: Precharged pressure for the this pump is 28-30 psi.

5.Prime the pump.

6.Reconnect power.

7.Close faucet.

RECOMMENDED FUSING & WIRING DATA - 60 HZ MOTORS

HP

VOLT

Dual

Element

Fuse 250V

Distance in Feet

From Meter to Motor

0

51

 

101

201

to

to

 

to

to

50

100

 

200

300

 

 

Wire Size

 

1/2

115

15

14

12

10

8

 

 

 

 

 

 

230

10

14

14

14

14

 

 

 

 

friction loss chart

 

 

 

 

 

 

 

Feet Friction Loss in 100 Feet of Plastic Pipe

 

 

 

 

 

 

Gallons Per Minute

 

 

 

 

Pipe Size

20

25

30

40

50

60

80

100

120

1-1⁄4”

5.6

8.5

11.9

20.2

30.5

 

 

 

 

1-1⁄2”

2.6

4.0

5.5

9.4

14.3

19.9

34.2

 

 

2“

1.2

1.6

2.8

4.2

5.8

9.9

15.0

21.2

 

2-1⁄2“

 

 

 

1.2

1.8

2.5

4.2

6.3

8.8