P250AF DIRECT SPAR ELECTRODE LOCATION
1/4” |
| 1/16” | 7/16” | 1/16” | |
+/- | (11.11 mm) | +/- (1.587 mm) | |||
(6.35 mm) | (1.587 mm) |
1/8” (3.175 mm) GAP
31/64” | +/- | 1/16” |
(12.3 mm) | (1.587 mm) |
P265DI
DIRECT SPARK IGNITION
HONEYWELL S87K SYSTEM
DIRECT SPARK IGNITION
HONEYWELL SYSTEM
Starting the burner:
1)Turn the gas valve control knob to “OFF”, wait five minutes.
2)Turn gas valve control knob to “ON”.
3)Set room thermostat above room temperature.
4)If burner does not light, SHUT OFF BURNER COMPLETELY AND WAIT FIVE MINUTES, then repeat steps 1 through 3 above.
To shut off burner:
1)Turn the gas valve control knob to “OFF”.
2)Turn off electrical supply.
DESCRIPTION
The Honeywell S87K (24VAC) Direct Spark Ignition Systems operate through a thermostat to provide a means of ignition for the main burner on
SEQUENCE OF OPERATION
On a call for heat, voltage is applied to the ignitor across Terminals 1 (power) and ^ (ground) of the input connector. A high voltage spark is then generated from the spark electrode to ground. Simultaneously, the gas valve is energized.
At the start of each heat cycle, there is a “Trial for ignition period” of three seconds duration. Normally main burner flamewill be established before the end of this period. Once the flame is established, sparking will cease and the “flame rod” will provide flame monitoring for the remainder of heat cycle. If the flame is extinguished during this cycle, the ignitor will start sparking automatically in an attempt to