Wayne P265F, P250AF-DI P250AF DIRECT SPAR ELECTRODE LOCATION, P265DI DIRECT SPARK IGNITION

Models: P265 P250AF P265-EP P250AF-DI P250AF-EP P265F

1 25
Download 25 pages 13.87 Kb
Page 17
Image 17
P250AF DIRECT SPAR ELECTRODE LOCATION

P250AF DIRECT SPAR ELECTRODE LOCATION

1/4”

 

1/16”

7/16”

1/16”

+/-

(11.11 mm)

+/- (1.587 mm)

(6.35 mm)

(1.587 mm)

1/8” (3.175 mm) GAP

31/64”

+/-

1/16”

(12.3 mm)

(1.587 mm)

P265DI

DIRECT SPARK IGNITION

HONEYWELL S87K SYSTEM

P250AF/P265-DI

DIRECT SPARK IGNITION

HONEYWELL SYSTEM

Starting the burner:

1)Turn the gas valve control knob to “OFF”, wait five minutes.

2)Turn gas valve control knob to “ON”.

3)Set room thermostat above room temperature.

4)If burner does not light, SHUT OFF BURNER COMPLETELY AND WAIT FIVE MINUTES, then repeat steps 1 through 3 above.

To shut off burner:

1)Turn the gas valve control knob to “OFF”.

2)Turn off electrical supply.

DESCRIPTION

The Honeywell S87K (24VAC) Direct Spark Ignition Systems operate through a thermostat to provide a means of ignition for the main burner on gas-fired equipment. This is accomplished by generating a spark between high voltage electrode and ground. Once the flame is established a flame rod monitors the main burner flame.

SEQUENCE OF OPERATION

On a call for heat, voltage is applied to the ignitor across Terminals 1 (power) and ^ (ground) of the input connector. A high voltage spark is then generated from the spark electrode to ground. Simultaneously, the gas valve is energized.

At the start of each heat cycle, there is a “Trial for ignition period” of three seconds duration. Normally main burner flamewill be established before the end of this period. Once the flame is established, sparking will cease and the “flame rod” will provide flame monitoring for the remainder of heat cycle. If the flame is extinguished during this cycle, the ignitor will start sparking automatically in an attempt to re-establish the flame. If this does not occur within the “Trial for ignition period,” the system will go into lockout, closing the gas valve.