FLUE PIPE AND CHIMNEY

The flue pipe should be carefully inspected and replaced if necessary in connection with installation of a draft hood. All installations must operate with a negative draft overfire. Refer to your local gas company or codes for assistance or to the furnace and/or boiler manufacturer for recommendations.

The flue pipe entrance into the chimney should be at least two feet (.610m) above the clean-out opening in the chimney.

The chimney should extend high enough above the dwelling or other neighboring obstructions so that wind from any direction will not strike the chimney from any angle above horizontal. Unless the obstruction is of greater magnitude, it is the usual experience that a chimney extending two feet above flat roofs or above fire wall parapets, and peaked roofs within 30 feet (9.144m) will be reasonably free of downdraft.

Where the chimney is unlined or where local experience indicates that flue gas condensate might be a problem, the local gas company should be consulted.

The chimney should be examined and thoroughly cleaned, if necessary, before installation is made to make sure it freely conduct the flue gases to the outside.

Flue pipe should extend through the chimney wall to inner face of chimney liner but not beyond, and should be firmly cemented to masonry. A thimble may be used to facilitate removal of flue pipe for cleaning, in which event the thimble should be permanently cemented in place with mortar or other fireproof material that will not crack or check the flue pipe or thimble, whichever is used, should be sealed into the chimney liner.

Flue connections from two or more appliances should not enter opposing or adjacent sides of the chimney at the same level.

Under no circumstances should the flue pipe be connected it to a flue of an open fireplace.

INSPECTION OF HEATING APPLIANCE

A careful inspection of furnace or boiler should be made. If cracked heating sections, leaking soft plugs or any other condition which might make the unit unsatisfactory for gas conversion is found, proper arrangements should be made for replacement or repair before proceeding with the burner installation. Cracked heating sections should be replaced.

A neutral pressure point adjuster, similar to the one shown in figure 2 may be installed in the flue pipe between the furnace and a conventional type CSA draft hood. The neutral pressure point adjustment should be left in the fully open position until after the burner rating has been established. The material used for flue pipe should be resistant to corrosion.

The necessity for installing a neutral pressure point adjuster as outlined above, may be eliminated by reducing the flue pipe and draft hood to the sizes shown in the table.

NOTE: For oil fired conversions consult boiler or furnace manufacturer. Appliance must maintain negative draft overfire.

Air Inet Opening 1 Sq. in. (645.2 mm2) for each 1,000 Btu (.2931 kW) per hour input.

Ventilating Air Opening 1 Sq. in. (645.2 mm2) for each 1,000 Btu (.2931 kW) per hour input.

Illustration showing air opening necessary to supply air for combustion when heating appliance is installed in an enclosed room.

Application located in confined spaces. Ventilation air from inside building - combustion and draft hood dilution air from outside. Ventilated attic or ventilated craw space.

NOTE: Ducts used for make-up air may be connected to the cold air return of the heat- ing system only if they connect directly to outdoor air.

Attic Ventilation Louvers are required at each end of attic with alternate air inlet No. 1.

1, 2, and 3 mark alternate loca- tions for air from outdoors. Free area shall be not less than 1 Sq. in. (645.2 mm2) per 5,000 Btu (.1.465 kW) per hour of the total per hour of the total input rating of all appliances in the enclosure.

Crawl-space Ventilation Louvers for unheated crawl space are required with alternate air inlet No. 3.

Each Ventilation Air Opening from inside the building shall have a free area of not less than 1 Sq. in. (645.2 mm2) per 5,000 Btu (.1.465 kW) per hour of the total per hour of the total input rating of all appliances in the enclosure.

FIGURE 1

2

Page 3
Image 3
Wayne P265-EP, P250AF-DI, P250AF-EP, P265F specifications Flue Pipe and Chimney, Inspection of Heating Appliance

P265, P250AF, P265-EP, P250AF-DI, P250AF-EP specifications

Wayne P265-EP, P250AF-EP, P250AF-DI, P265F, and P265 are a series of fuel dispensing pumps known for their reliability and advanced technology. These pumps are engineered to meet the demanding needs of various fueling environments, making them suitable for both commercial and retail operations.

The Wayne P265-EP is particularly notable for its compact design and efficient performance. It features a user-friendly interface, making it easy for operators to manage fuel dispensing. Its electronic controller allows for precise monitoring and control of fuel flow, ensuring accurate transactions while minimizing wastage. The pump is also equipped with advanced security features to prevent unauthorized access.

The P250AF-EP and P250AF-DI models are designed with versatility in mind. They can support multiple fuel types, including gasoline, diesel, and biofuels, providing flexibility for businesses looking to serve a diverse clientele. The integrated diagnostics system helps operators identify issues quickly, reducing downtime and enhancing operational efficiency. Additionally, these models incorporate Wayne's SmartServe technology, which optimizes service intervals and maintenance schedules.

The P265F model emphasizes high performance and durability. Constructed with robust materials, it withstands harsh environmental conditions, making it ideal for outdoor installations. Featuring an advanced filtration system, it enhances fuel quality by removing contaminants, thereby extending the lifespan of both the pump and the connected storage tanks. Enhanced hydraulic efficiency translates to faster fueling times, increasing customer satisfaction at busy fueling stations.

Lastly, the P265 model stands out for its automatic nozzle shut-off function, which significantly reduces the risk of overfills and spills. This feature safeguards both the environment and the business against potential liabilities associated with fuel spillage.

In summary, the Wayne P265-EP, P250AF-EP, P250AF-DI, P265F, and P265 pumps incorporate cutting-edge technologies that prioritize efficiency, safety, and user convenience. Their advanced features ensure reliable performance across a variety of fueling applications, making them a preferred choice for operators seeking high-quality dispensing solutions. Whether it's speed, security, or flexibility, Wayne pumps are engineered to meet the evolving needs of the fuel distribution industry.