GAS SUPPLY

19

 

 

GAS LINE PIPING

Refer to the piping chart at the bottom of previous page.

The corrugated gas line from the manifold is 58 inches long. Do not extend the gas line.

We have provided the means to make an SAE 45° fl are connection. Do not use pipe sealant on this connection.

If the length of line required does not exceed 50 feet, use a 5/8” O.D. tube. One size larger should be used for lengths greater than 50 feet. Refer to piping chart.

Gas piping may be copper tubing, type K or L; polyethylene plastic tube, with a minimum wall thickness of .062 inch; or standard weight (schedule 40) steel or wrought iron pipe.

Copper tubing must be tin-lined if the gas contains more than 0.3 grams of hydrogen sulfi de per 100 cubic feet of gas.

Plastic tubing is suitable only for outdoor, underground use.

Gas piping in contact with earth, or any other material which may corrode the piping, must be protected against corrosion in an approved manner.

Underground piping must have a minimum of 18” cover.

TEST CONNECTIONS

All connections and joints must be thoroughly tested for leaks in accordance with local codes and all listed procedures in the latest edition of the National Fuel Gas Code ANSI Z223.1/NFPA 54.

DANGER

Do not use an open flame to check for gas leaks. Be sure there are no sparks or open flames in the area while you check for gas leaks. This will result in a fire or explosion which can cause serious bodily injury or death, and damage to property.

CONNECT GAS SUPPLY

A 58 inch corrugated gas line is supplied with the grill. This line needs to pass through the gas inlet opening to the main gas supply.

1)Connect the corrugated gas line to the regulator (a). Use the 1/2” fl ared gasket (1) to ensure proper seal.

(b) Shows the gas line and regulator assembled.

2)Uncap the fl are fi tting connection off the regulator.

3)Hard pipe the gas supply to the inlet of the regulator. Refer to “Typical Gas Supply Installation”.

top view

Cap

 

(Optional Side Burner)

Corrugated Gas Line

Hard piped

to Manifold

gas supply

 

(1)

 

 

 

 

Regulator

 

 

 

 

 

 

 

 

 

 

a.

 

 

 

 

 

 

 

top view

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Optional Side Burner)

Corrugated Gas Line

Hard piped

 

 

 

to Manifold

gas supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Regulator

b.

ATTENTION: This product has been safety tested and is only certified for use in a specific country. Refer to label located on outer carton for country designation.

These parts may be gas carrying or gas burning components. Please contact Weber-Stephen Products Co., Customer Service Department for genuine Weber-Stephen Products Co. replacement part(s) information.

WARNING: Do not attempt to make any repair to gas carrying or gas burning components without contacting Weber-Stephen Products Co., Customer Service Department. Your actions, if you fail to follow this product Warning, may cause a fire or an explosion resulting in serious personal injury or death and damage to property.