Weil-McLain 550-110-260/0107 11d Troubleshooting — control module lights, Is POWER light off?

Models: 550-110-260/0107

1 64
Download 64 pages 7.9 Kb
Page 47
Image 47
11d Troubleshooting — control module lights

GOLD CGs Gas-Fired Water Boiler — Boiler Manual CHART 1 — Troubleshooting POWER light status

11d Troubleshooting — control module lights

CHART 1 — Troubleshooting POWER light status

— Usually indicates reversed 120 VAC polarity if POWER light flashes by itself —

Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.

Is POWER light off?

 

No

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is POWER light...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashing

Flashing with

 

On steady

 

 

alone

another light

 

(not flashing)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TSTAT CIRC

 

Chart 2

 

 

 

 

 

light flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESS SWITCH

 

Chart 3

 

Chart 5

 

 

light flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLAME

 

Chart 4

 

Chart 6

 

 

light flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For insufficient heat or no heat problem, go to Chart 7 if POWER light is on steady, with no other Is POWER light off? light flashing.

Usually indicates polarity on incoming 120 VAC power line is wrong.

TURN OFF POWERat service switch or breaker, then reverse the HOT and NEUTRAL wires entering the boiler in the J-box.

Restore POWER at service switch or breaker.

Is POWER light flashing now?

No

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

Have system checked by a

 

 

 

licensed electrician.

 

 

 

If problem persists, call your

 

 

 

Boiler should now

 

local Weil-McLain sales

operate normally.

 

representative.

 

 

 

 

 

Make sure service switch or circuit breaker is on or fuses are good.

Remove 120 VAC IN plug (Figure 25, item 3, page 46) on control module.

Using voltmeter, check across top and bottom pins of 120 VAC IN plug.

Does voltmeter indicate 120 VAC?

No

Yes

 

 

Problem is with incoming electricity. Have licensed electrician repair circuit.

Reconnect 120 VAC IN plug.

Remove 120 VAC transformer PRIMARY plug (Figure 25, item 2, page 46) on control module.

Using voltmeter, check across top and bottom pins of PRIMARY receptacle.

Does voltmeter indicate 120 VAC?

No

Yes

 

 

Replace control module.

Retest.

Reinstall 120 VAC transformer PRIMARY plug.

Remove 24 VAC transformer plug (Figure 25, item 5, page 46) on control module.

Using voltmeter, check across pins of receptacle.

Does voltmeter indicate 24 VAC?

No

Yes

 

 

Replace transformer.

 

Replace control module.

Retest.

 

Retest.

 

 

 

Part number 550-110-260/0107

47

Page 47
Image 47
Weil-McLain 550-110-260/0107 11d Troubleshooting — control module lights, GOLD CGs Gas-FiredWater Boiler — Boiler Manual