GOLD CGs Gas-Fired Water Boiler — Boiler Manual

11b Troubleshooting — air pressure switch

Air pressure switch

Table 6 Pressure switch setpoint

Make sure boiler water temperature is 100 °F or cooler before starting procedure to obtain appropriate readings.

Check pressure switch setting

1.See Figure 24 and Table 6.

2.Remove both air pressure switch hoses from air pressure switch.

3.Install tees and tubing as shown in Figure 24 to inclined manometer.

4.Turn off gas valve and set thermostat to call for heat. Inducer will run but burners will not ignite.

5.Check for 24 VAC between both air pressure switch terminals and ground.

6.If manometer reading is above the setpoint of the switch (see Table 6), but there is not 24 VAC between both air pressure switch terminals and ground

— replace air pressure switch.

Figure 24  Manometer connections

(for elevations above 2,000 ft, contact your local Weil-McLain sales office for details.)

Troubleshooting air pressure reading

1.If manometer reading is lower than the setpoint of the switch (see Table 6) — check for possible causes:

blockage in hoses

obstruction in inducer housing outlet

loose inducer wheel on motor shaft

inducer motor not in proper rpm

inducer back plate not sealed properly

blockage in block assembly

blockage in flue pipe or termination

incorrect pressure switch

Return to normal operation

When pressure reading is correct and air pressure switch is operating properly — remove tees and reinstall hoses

The boiler will not operate cor- rectly unless pressure switch hoses are correctly located. The red hose connects from the right side (negative) hose barb to the flue collector. The white hose connects from the left side (positive) hose barb of the switch to the connector box (between flue collector and inducer) as shown in

Figure 24.

44

Part number 550-110-260/0107

Page 44
Image 44